Table 67. Pump parameters (Cont.).
Interlock enabled
P9.3.9
b
Minimum value:
N.A.
Options:
0 = Disabled; or
1 = Enabled.
This parameter enables the drive to look at the digital input interlocks to tell which motor is available for running or if they were brought
Description:
offline.
Recovery method
P9.3.10
ab
Minimum value:
N.A.
Options:
0 = Automatic; or
1 = Stop.
Description:
This parameter is for the slave when multi-drive system lost the master. The slave drive can continue run if it set to be "Automatic".
However, the slave drive will stop immediately if it is set to be "Stop".
Add/remove drive selection
P9.3.11
b
Minimum value:
N.A.
0 = Drive ID; or
Options:
1 = Run time.
Description:
In default, MPFC system will add/remove pump according to their drive ID, from small to large. The order can also depend on each slave
drive's running time: add the drive that has shortest running time and remove the drive that has longest running time first.
Run time enabled
P9.3.12
b
N.A.
Minimum value:
Options:
0 = Disabled; or
1 = Enabled.
Description:
The run time counter will start counting only if this parameter is enabled.
Run time limit
P9.3.13
b
0.0 h
Minimum value:
Description:
If drive run time is over this limit, its network status will be "Need Alternation". Limit equals 0 means run time counter disabled.
P9.3.14
Run time reset
N.A.
Minimum value:
Options:
0 = No action; or
1 = Reset.
Description:
One-time parameter, set to be 1 will clear run time counter.
Master drive mode
P9.3.15
b
N.A.
Minimum value:
Options:
0 = Follow PI;
1 = Fixed speed; or
2 = Turn off.
Defines how the master drive will maintain the frequency control when slaves are brought in; follow PI, fixed speed, or turn off.
Description:
Master fixed speed
P9.3.16
b
Minimum value:
MinFreq Hz
Description:
Defines the fixed speed frequency when the master drive mode is set for fixed speed control when slaves are brought in.
Master fixed speed delay
P9.3.17
b
0 s
Minimum value:
Description:
Defines the delay time before the master drive begins running at the fixed speed or turns off if the master mode is set for fixed speed
or turn off.
POWERXL DM1 SERIES VARIABLE FREQUENCY DRIVES
Maximum value:
N.A.
Maximum value:
N.A.
Maximum value:
N.A.
N.A.
Maximum value:
300,000.0 h
Maximum value:
N.A.
Maximum value:
N.A.
Maximum value:
Maximum value:
MaxFreq Hz
1,000 s
Maximum value:
Chapter 7- Multi-purpose application
Default value:
Default value:
Default value:
Default value:
Default value:
Default value:
Default value:
Default value:
Default value:
MN040049EN—September 2021 www.eaton.com
ID 350
0
ID 2285
0
ID 2311
0
ID 2280
0
ID 2281
0.0 h
ID 2283
N.A.
ID 2473
0
ID 2474
50.00 Hz
ID 2475
5 s
211