Table 46. PI Controller (Cont.).
PI dead band delay
P7.1.8
b
Minimum value:
0.00 s
Description:
If the PI process value goes out of the dead band area for the desired time delay, at that point the controller will re-initialize and try to
level out again.
PI ramp time
P7.1.9
b
0.00 s
Minimum value:
Description:
Defines the rising and falling ramp times for changes in the process value.
Parameter value can only be changed after the drive has stopped.
a
Parameter value will be set to be default when changing macros.
b
Table 47. Setpoint (Cont.).
.
P7.2.1 - Standard.
PI keypad setpoint 1
P7.2.1.1
b
Minimum value:
PI Process Unit Min
Description:
Keypad PI reference value setpoint 1.
PI keypad setpoint 2
P7.2.1.2
b
PI Process Unit Min
Minimum value:
Description:
Keypad PI reference value setpoint 2.
PI wake-up action
P7.2.1.3
b
Minimum value:
N.A.
0 = Wake-up when below wake-up level.
Options:
1 = Wake-up when above wake-up-level.
2 = Wake-up when below wake-up level % from PI setpoint.
3 = Wake-up when above wake-up level %from PI setpoint.
Description:
This parameter defines the wake-up function action.
P7.2.2 - Setpoint 1.
PI setpoint 1 source
P7.2.2.1
a
Minimum value:
N.A.
0 = Not used;
Options:
1 = PI keypad setpoint 1;
2 = PI keypad setpoint 2;
3 = AI;
4 = Drive reference pot;
5 = FB process data input 1;
6 = FB process data input 2;
7 = FB process data input 3;
8 = FB process data input 4;
9 = FB process data input 5;
10 = FB process data input 6;
11 = FB process data input 7;
12 = FB process data input 8;
13 = FB PI setpoint 1; or
14 = FB PI setpoint 2.
Description:
Defines source of the setpoint value the drive uses. This can either be an internal preset value, keypad setpoint, analog signal, or
fieldbus message.
PI setpoint 1 sleep enable
a
P7.2.2.2
Minimum value:
N.A.
Options:
0 = Disabled; or
1 = Enabled.
This function will disable the output when the frequency drops below the sleep frequency for the sleep delay time. The output
Description:
re-engages when feedback rises above the wake-up level.
122
POWERXL DM1 SERIES VARIABLE FREQUENCY DRIVES MN040049EN—September 2021 www.eaton.com
Maximum value:
320.00 s
300.00 s
Maximum value:
Maximum value:
PI Process Unit Max
PI Process Unit Max
Maximum value:
Maximum value:
N.A.
Maximum value:
N.A.
Maximum value:
N.A.
ID 1306
Default value:
0.00 s
ID 1311
0.00 s
Default value:
ID 1307
Default value:
0.00 varies
ID 1309
0.00 varies
Default value:
ID 2466
Default value:
0
ID 1312
Default value:
1
ID 1315
Default value:
0

Advertisement