Table 60. Drive control (Cont.).
DC brake current
P4.2.2
ab
Minimum value:
DriveNomCurrCT*15/100
A
Description:
Defines the current level injected into the motor during DC-braking.
Start DC brake time
P4.2.3
ab
0.00 s
Minimum value:
Description:
This parameter defines the time the drive injects DC braking current before starting to ramp. This can be used to stop motors that are
potentially spinning before a run command is
spinning before a run command is given.
Stop DC brake frequency
P4.2.4
ab
0.10 Hz
Minimum value:
Description:
During a ramp to stop, this parameter defines the output frequency to be below to begin DC braking.
Stop DC brake time
P4.2.5
ab
Minimum value:
0.00 s
Determines the length of DC braking while stopping.
Description:
0.00 = DC brake is not used; or
>0.0 = The amount of time DC-braking will occur after falling below the stop DC brake frequency.
POWERXL DM1 SERIES VARIABLE FREQUENCY DRIVES
Maximum value:
DriveNomCurrCT*15/10
A
600.00 s
Maximum value:
given or
before ramping to reference level. This is to stop motors that are potentially
10.00 Hz
Maximum value:
Maximum value:
600.00 s
f out
Output Frequency
Motor Speed
DC Braking ON
t = 1 x Stop DC Brake Time
Run
Stop
DC braking time when stop mode = coasting.
f out
Motor Speed
Output Frequency
P14.3
Run
Stop
DC braking time when stop mode = ramp.
Chapter 7- Multi-purpose application
Default value:
Default value:
Default value:
Default value:
t
DC-Braking
t
t = Stop DC Brake Time
MN040049EN—September 2021 www.eaton.com
ID 254
DriveNomCurrCT*1/2 A
ID 263
0.00 s
ID 262
1.50 Hz
ID 255
0.00 s