Table 40. Parameters (Cont.).
.
P1 - Basic parameters.
Minimum frequency
P1.1
b
Minimum value:
0.00 Hz
Defines the lowest frequency at which the drive will operate. This setting will limit other frequency parameter settings.
Description:
1 = Fire mode minimum frequency.
2 = Derag.
3 = MPFC staging frequency.
4 = MPFC master fixed frequency.
5 = Prime pump frequency.
6 = Prime pump frequency 2.
Maximum frequency
P1.2
b
0.00 Hz
Minimum value:
Description:
Defines the highest frequency at which the drive will operate. This will limit other frequency parameters.
1 = Keypad reference.
2
= Motor potentiometer.
3 = Jog speed.
4 = 2nd stage ramp frequency.
5 = Fire mode minimum frequency.
6 = Derag.
7 = MPFC staging frequency.
8 = MPFC master fixed frequency.
9 = Prime pump frequency.
10 = Prime pump frequency 2.
11 = Preset speed frequency.
12 = Frequency limit value.
13 = Reference limit value.
14 = Speed control_fs2.
15 = Stall frequency limit.
16 = 4 mA fault frequency.
17 = MPFC de-staging frequency.
18 = Pipe fill loss frequency low.
19 = Pipe fill loss frequency high.
20 = Broken pipe frequency limit.
Accel. time 1
P1.3
b
0.1 s
Minimum value:
Description:
Defines the time required for the output frequency to accelerate from zero frequency to maximum frequency.
Decel. time 1
P1.4
b
Minimum value:
0.1 s
Defines the time required for the output frequency to decelerate from maximum frequency to zero frequency.
Description:
Motor nom. current
a
P1.6
Minimum value:
DriveNomCurrCT*1/10 A
Description:
Motor nameplate rated full load current. This value is found on the rating plate of the motor.
Motor nom. speed
P1.7
a
300 rpm
Minimum value:
Description:
Motor nameplate rated speed. This value is found on the rating plate of the motor.
Motor PF
P1.8
a
Minimum value:
0.30
Motor nameplate rated power factor. This value is found on the rating plate of the motor.
Description:
Motor nom. voltage
P1.9
a
Minimum value:
180 V
Description:
Motor nameplate rated voltage. This value is found on the rating plate of the motor.
Motor nom. frequency
P1.10
a
8.00 Hz
Minimum value:
Description:
Motor nameplate rated frequency. This value is found on the rating plate of the motor.
POWERXL DM1 SERIES VARIABLE FREQUENCY DRIVES MN040049EN—September 2021 www.eaton.com
Maximum value:
400.00 Hz
400.00 Hz
Maximum value:
3,000.0 s
Maximum value:
Maximum value:
3,000.0 s
Maximum value:
DriveNomCurrCT*2 A
20,000 rpm
Maximum value:
Maximum value:
1.00
Maximum value:
690 V
400.00 Hz
Maximum value:
Chapter 6 - Pump control application
ID 101
Default value:
0.00 Hz
ID 102
MaxFreqMFG
Default value:
ID 103
20.0 s
Default value:
ID 104
Default value:
20.0 s
ID 486
Default value:
DriveNomCurrCT A
ID 489
MotorNomSpeedMFG
Default value:
ID 490
Default value:
0.85
ID 487
Default value:
MotorNomVoltMFG V
ID 488
MotorNomFreqMFG Hz
Default value:
101