Table 60. Drive control (Cont.).
Skip F3 low limit
P4.3.6
b
Minimum value:
0.00 HZ
Description:
Defines the acceleration/deceleration time when the output frequency is between the selected prohibit frequency range limits. The
ramping speed (selected acceleration/deceleration time 1 or 2) is multiplied with this factor: e.g., value 0.1 makes the acceleration time
10 times shorter than outside the prohibit frequency range limits.
Skip F3 high limit
P4.3.7
b
SkipRange3LowLimit HZ
Minimum value:
Description:
Defines the acceleration/deceleration time when the output frequency is between the selected prohibit frequency range limits. The
ramping speed (selected acceleration/deceleration time 1 or 2) is multiplied with this factor: e.g., value 0.1 makes the acceleration time
10 times shorter than outside the prohibit frequency range limits.
P4.4 - Energy savings calculations.
Currency
P4.4.1
b
Minimum value:
N.A.
0 = $;
Options:
1 = £;
2 = €;
3 = ¥;
4 = Rs;
5 = R$;
6 = Fr; or
7 = kr.
Description:
Sets the local currency used for energy savings estimation.
Energy cost
P4.4.2
b
Minimum value:
Varies
Description:
Sets the local energy cost per kW. Used for energy savings estimation.
Data type
P4.4.3
b
Minimum value:
N.A.
Options:
0 = Cumulative;
1 = Daily average;
2 = Weekly average;
3 = Monthly average; or
4 = Yearly average.
Description:
Selects the format to view energy savings. The drive takes four recordings in an hour and then calculates the average based off this
parameter. The savings estimation is based on comparing the drives energy usage compared to a across the line starter.
P4.4.4
Energy savings reset
N.A.
Minimum value:
Options:
0 = Not reset; or
1 = Reset.
Description:
Resets the energy savings value.
Parameter value can only be changed after the drive has stopped.
a
Parameter value will be set to be default when changing macros.
b
POWERXL DM1 SERIES VARIABLE FREQUENCY DRIVES
Maximum value:
SkipRange3HighLimit Hz
400.00 Hz
Maximum value:
Maximum value:
N.A.
Maximum value:
Varies
Maximum value:
N.A.
N.A.
Maximum value:
Chapter 7- Multi-purpose application
Default value:
Default value:
Default value:
Default value:
Default value:
Default value:
MN040049EN—September 2021 www.eaton.com
ID 260
0.00 Hz
ID 261
0.00 Hz
ID 2122
0
ID 2123
0.00 varies
ID 2124
0
ID 2125
N.A.