Page 1
PowerXL DG1 Series VFD Effective September 2016 Supersedes May 2014 Communication manual...
Page 2
CONTENTS OF THIS DOCUMENT SHALL NOT BECOME PART OF OR MODIFY ANY CONTRACT BETWEEN THE PARTIES. In no event will Eaton be responsible to the purchaser or user in contract, in tort (including negligence), strict liability, or otherwise for any special, indirect, incidental, or consequential damage or loss whatsoever, including but not limited to...
Page 3
PowerXL DG1 Series VFD Support services Support services The goal of Eaton is to ensure your greatest possible satisfaction with the operation of our products. We are dedicated to providing fast, friendly, and accurate assistance. That is why we offer you so many ways to get the support you need.
DIP or failure. charge in the capacitors, these parts may still be live This should not cause dangerous operating states even after disconnection. Fit appropriate warning signs xiii POWERXL DG1 SERIES VFD MN040010EN—September 2016 www.eaton.com...
Contact with this performing maintenance voltage is extremely dangerous and may cause death Be sure equipment is properly earthed • or severe injury. Wear safety glasses whenever working on electronic • controllers or rotating machinery POWERXL DG1 SERIES VFD MN040010EN—September 2016 www.eaton.com...
Page 15
A hard Before applying power to this drive, make sure that copy of this information may be ordered from Eaton the front and cable covers are closed and fastened to literature fulfillment.
Page 16
Do not attempt to install or remove the MOV or EMC • of the equipment grounding conductor must be at least screws while power is applied to the drive’s input 10 mm2 Cu. Drive requires that only copper conductor should terminals. be used. POWERXL DG1 SERIES VFD MN040010EN—September 2016 www.eaton.com...
For more technical information, contact the factory or your local Eaton sales representative. xvii POWERXL DG1 SERIES VFD MN040010EN—September 2016 www.eaton.com...
Page 18
• norme CEI/EN 60204-1 doivent être efficace dans tous les modes de fonctionnement des dispositifs d’automatisation. Le déverrouillage des dispositifs d’arrêt d’urgence ne doit pas entraîner un redémarrage xviii POWERXL DG1 SERIES VFD MN040010EN—September 2016 www.eaton.com...
Page 19
MISE EN GARDE peut, si elle n’est pas évitée, entraîner des conséquences graves. Des mesures de sécurité importantes sont décrites dans les MISES EN GARDE (ainsi que dans les AVERTISSEMENTS). POWERXL DG1 SERIES VFD MN040010EN—September 2016 www.eaton.com...
Page 20
Ce support doit être conservé avec cet appareil à tout précaution peut entraîner la mort ou des blessures graves. moment. Une copie papier de ces informations peut être commandée auprès du service de documentation Eaton. POWERXL DG1 SERIES VFD MN040010EN—September 2016 www.eaton.com...
Page 21
Les entrées anti-rebond ne sont pas permises dans le schéma du circuit de sécurité. Des disjoncteurs de courant résiduel (RCD) ne peuvent être installés qu’entre le réseau de courant alternatif et l’entraînement. POWERXL DG1 SERIES VFD MN040010EN—September 2016 www.eaton.com...
Page 22
S’assurer que les bornes de sortie de l’entraînement (U, V, et CEM lorsque l’alimentation est appliquée aux bornes W) ne sont pas connectées à l’alimentation secteur, ce qui d’entrée de l’entraînement pourrait causer de graves dommages à l’entraînement. xxii POWERXL DG1 SERIES VFD MN040010EN—September 2016 www.eaton.com...
Page 23
E/S de l’entraînement. Le nombre de cycles de charge représentant commercial Eaton local. maximum permis des condensateurs CC (c’est-à-dire les mises sous tension par application de puissance) est de cinq en dix minutes. xxiii POWERXL DG1 SERIES VFD MN040010EN—September 2016 www.eaton.com...
To activate the real time clock (RTC) functionality in the This series overview describes the purpose and contents of PowerXL DG1 Series VFD, the RTC battery (already mounted this manual, the receiving inspection recommendations and in the drive) must be connected to the control board.
Powerxl series overview Rating label General information The DGI Series Drives from Eaton’s electrical business provides a wide selection of option boards to increase the Figure 2. Rating label number and type of control inputs and outputs (I/O) and communication interfaces to provide the versatility required for today’s demanding motor control applications.
Optional Card A Optional Card B Control I/O Terminals RS-485 Termination Resistor Removable MOV Screw Removable EMC Screw Motor Ground Clamp Location Line Ground Clamp Location Grounding Strap Location Grounding Strap Location Line Side Motor POWERXL DG1 SERIES VFD MN040010EN—September 2016 www.eaton.com...
AFD via the communication parameters. The electrical connection between master and the slaves connected in parallel are implemented via the serial interface A-B (A = negative, B = positive) with a shielded RS-485 twisted pair cable. POWERXL DG1 SERIES VFD MN040010EN—September 2016 www.eaton.com...
When the slave sends its response, it places its own address in this address field of the response to let the master know which slave is responding. POWERXL DG1 SERIES VFD MN040010EN—September 2016 www.eaton.com...
Number of coils Low 0x03 Two kinds of checksum are used for standard Modbus CRC High 0x7E networks. The error checking field contents depend upon CRC Low 0x25 the transmission method that is being used. POWERXL DG1 SERIES VFD MN040010EN—September 2016 www.eaton.com...
Starting address 0x07D0 hex (= 2000) Start address Low 0xD0 Number of Input Registers Number of Input 0x00 0x0003 hex (= 3) Registers High Number of Input 0x03 Registers Low CRC High 0xB2 CRC Low 0x25 POWERXL DG1 SERIES VFD MN040010EN—September 2016 www.eaton.com...
The binary outputs in the previous example corre- spond to the outputs in the following way. Table 18. Binary bits and corresponding outputs Output 26 25 24 23 22 21 20 19 — — — — — 28 27 POWERXL DG1 SERIES VFD MN040010EN—September 2016 www.eaton.com...
(e.g., Torque reference). With the Status Word (SW) read by the Master, the status of the device can be seen. Actual Value (ACT) and PD1–PD8 show the other actual values. POWERXL DG1 SERIES VFD MN040010EN—September 2016 www.eaton.com...
See Process Data IN section for setup. 10–15 Not in use Not in use Fb general control word The DG1 does not use the FB General Control Word. The main control word is used to provide commands to the drive. POWERXL DG1 SERIES VFD MN040010EN—September 2016 www.eaton.com...
Faulted — Warning — Ref. frequency not reached Ref. frequency reached Bypass activated Bypass not activated Run Enable Run disable Not in use Not in use Not In use 9–15 Not in use POWERXL DG1 SERIES VFD MN040010EN—September 2016 www.eaton.com...
1. Set FB control word (Modbus Address 42000) value to 0hex to 1hex 6. DG1 status is STOP 2. DG1 status is RUN 3. Set FB Speed reference (Modbus Address 42002) value to 5000 (= 50.00%) POWERXL DG1 SERIES VFD MN040010EN—September 2016 www.eaton.com...
Modbus/TCP , and it is only used when one IP address indicator in the sequence, followed by any Network Status stands for several endpoints. indicators present. After completion of this power up test, the indicator(s) will turn to a normal operational state. POWERXL DG1 SERIES VFD MN040010EN—September 2016 www.eaton.com...
Exclusive Owner connections are established. Steady Red Major fault PowerXL has detected a non-recoverable major fault. Self-test PowerXL is performing its power up testing. Flashing Green/Red Flash rate is 1 flash per second. POWERXL DG1 SERIES VFD MN040010EN—September 2016 www.eaton.com...
IP Address Mode 1500 0 = Static IP P20.3.1 1 = DHCP with AutoIP Active IP Address 1507 P20.3.2 Active Subnet Mask 1509 P20.3.3 Active Default Gateway 1511 P20.3.4 MAC Address 1513 P20.3.5 POWERXL DG1 SERIES VFD MN040010EN—September 2016 www.eaton.com...
Page 43
IP port, a fieldbus error is generated immediately. Modbus RTU. This Unit Identifier is used to communicate via devices such as bridges, routers and gateways that use a single IP address to support multiple independent Modbus end units. POWERXL DG1 SERIES VFD MN040010EN—September 2016 www.eaton.com...
Change in IP address mode will require PowerXL to mode configurations will be loaded. power cycle to get this change effective. Also ensure device MAC address (Keypad menu. P20.3.5) Figure 14. Static IP mode POWERXL DG1 SERIES VFD MN040010EN—September 2016 www.eaton.com...
Modbus TCP On-Board communications 2. Using PowerXL drive keypad, set the IP address in the PowerXL EIP to the desired address setting by. a. Setting Static IP Address Figure 15. Static IP address POWERXL DG1 SERIES VFD MN040010EN—September 2016 www.eaton.com...
4. Using PowerXL drive keypad, read “Active IP Address” (Keypad menu. P20.3.2), “Active Subnet Mask” (Keypad menu. P20.3.3), “Active Default Gateway” (Keypad menu. P20.3.4) parameters to ensure that IP address has been set to desired IP address. POWERXL DG1 SERIES VFD MN040010EN—September 2016 www.eaton.com...
CRC Low 0x83 Start address Low 0xD0 Number of Holding Registers Number of Holding 0x00 0x0003 hex (= 3) Registers High Number of Holding 0x03 Registers Low CRC High 0x07 CRC Low 0xE5 POWERXL DG1 SERIES VFD MN040010EN—September 2016 www.eaton.com...
The binary outputs in the previous example correspond to the outputs in the following way. Table 48. Binary bits and corresponding outputs Output 26 25 24 23 22 21 20 19 — — — — — — 28 27 POWERXL DG1 SERIES VFD MN040010EN—September 2016 www.eaton.com...
(e.g., Torque reference). With the StatusWord (SW) read by the Master, the status of the device can be seen. Actual Value (ACT) and PD1–PD8 show the other actual values. POWERXL DG1 SERIES VFD MN040010EN—September 2016 www.eaton.com...
(P1.2). This value has 2 decimal places in it. Process data in 1 to 8 Process Data In values 1 to 8 can be used in applications for various purposes. See below Process Data IN section for setup. POWERXL DG1 SERIES VFD MN040010EN—September 2016 www.eaton.com...
14 13 12 11 10 MSB — — — — — — — — — — — — — — LSB This is the Actual Speed of the motor.This value comes back in the form of % POWERXL DG1 SERIES VFD MN040010EN—September 2016 www.eaton.com...
Process Data IN7 0.01% 2010 Process Data IN8 0.01% 2011 ote: Process Data IN1 through Process Data IN8 change based off the selected application. See Appendix B for layout. POWERXL DG1 SERIES VFD MN040010EN—September 2016 www.eaton.com...
Overlapping IP addresses can cause conflicts between appliances. For more information about setting IP addresses, see “Manual IP Address Configuration” on Page 21. EtherNet/IP is a trademark of the Open DeviceNet Noee: Vendor Association (ODVA). POWERXL DG1 SERIES VFD MN040010EN—September 2016 www.eaton.com...
After completion of this power up test, the indicator (s) will turn to a normal operational state. Yellow LED on the ethernet jack is OFF when link speed is 10 mbps POWERXL DG1 SERIES VFD MN040010EN—September 2016 www.eaton.com...
Exclusive Owner connections are established. Steady red Duplicate IP address PowerXL has detected a Duplicate IP. Flashing green/red Self-test PowerXL is performing its power on self test. Flash rate is 1 flash per second. POWERXL DG1 SERIES VFD MN040010EN—September 2016 www.eaton.com...
CIP provides users with unified communication architecture throughout the manufacturing enterprise. 2. Machine to machine (industrial environment, fast communication) Industrial Environment Figure 21. Machine oN machine (indusorial envirNnmeno, faso cNmmunicaoiNn) POWERXL DG1 SERIES VFD MN040010EN—September 2016 www.eaton.com...
192.168.1.1 1505 P20.3.9 EtherNet/IP Protocol Status 0 = Off 1 = Operational 2 = Faulted P20.3.10 Connection Limit P20.3.19 EIP Fault Response 2518 0 = In Fieldbus Control 1 = in all Control POWERXL DG1 SERIES VFD MN040010EN—September 2016 www.eaton.com...
Defines how much time can pass from the last received message from the client device before fieldbus fault is generated. Default communication timeout is 10seconds. Noee: If the network cable is broken from PowerXL EtherNet/IP slot, a fieldbus error is generated immediately. POWERXL DG1 SERIES VFD MN040010EN—September 2016 www.eaton.com...
Change in IP address mode will require PowerXL to configurations will be loaded. power cycle to get this change effective. Also ensure device MAC address (Keypad menu. P20.3.5) Figure 23. Soaoic IP mNde POWERXL DG1 SERIES VFD MN040010EN—September 2016 www.eaton.com...
EtherNet/IP On-Board communications 2. Using PowerXL drive keypad, set the IP address in the PowerXL EIP to the desired address setting by: a. Setting Static IP Address Figure 24. Soaoic IP address POWERXL DG1 SERIES VFD MN040010EN—September 2016 www.eaton.com...
4. Using PowerXL drive keypad, read “Active IP Address” (Keypad menu. P20.3.2), “Active Subnet Mask” (Keypad menu. P20.3.3), “Active Default Gateway” (Keypad menu. P20.3.4) parameters to ensure that IP address has been set to desired IP address. POWERXL DG1 SERIES VFD MN040010EN—September 2016 www.eaton.com...
Select windows Start → All Programs. Open RSLogix 5000. From the Tools drop-down menu, select EDS Hardware Installation Tool to install the PowerXL Drive EtherNet/ IP EDS file. This file can be downloaded from the Eaton website. POWERXL DG1 SERIES VFD MN040010EN—September 2016 www.eaton.com...
Page 64
EtherNet/IP On-Board communications Select “New” from “File” menu. New controller window will pop-up. Select the controller and assign unique name. POWERXL DG1 SERIES VFD MN040010EN—September 2016 www.eaton.com...
Page 65
EtherNet/IP On-Board communications Press OK. Right-click on Ethernet. Select “New Module. ” Noee: PC on which RSLogix (master) is running and PowerXL device (slave) should be connected in same network. POWERXL DG1 SERIES VFD MN040010EN—September 2016 www.eaton.com...
Page 66
EtherNet/IP On-Board communications “Select Module Type” window will pop-up. Select “PowerXL DG1” (use filter to search PowerXL from catalog). POWERXL DG1 SERIES VFD MN040010EN—September 2016 www.eaton.com...
Page 67
You must change the class1 connection from provided default option by using “Change” button available on “New Module” window. This can also be done after adding the device under Ethernet by double-clicking on it. POWERXL DG1 SERIES VFD MN040010EN—September 2016 www.eaton.com...
Page 68
EtherNet/IP On-Board communications Choose the INT data type then select /IO connection from the provided list. After selecting desired I/O assembly instance connection, information related to it will appear. POWERXL DG1 SERIES VFD MN040010EN—September 2016 www.eaton.com...
Page 69
EtherNet/IP On-Board communications After selecting the I/O connection, click “OK. ” For this example, I/O connection ASM23OT-73TO will be used. The module definition window will then look as follows. POWERXL DG1 SERIES VFD MN040010EN—September 2016 www.eaton.com...
Page 70
EtherNet/IP On-Board communications After pressing “OK, ” the following warning will pop-up. Press “Yes. ” Warning snapshot. POWERXL DG1 SERIES VFD MN040010EN—September 2016 www.eaton.com...
Page 71
Then select “OK” on the New Module Window and the PowerXL drive will be added to the EtherNet/IP Network on the left, in this case under the CompactLogix EtherNet/IP master port as shown. Close the Select Module Type window or add more devices to the Network. POWERXL DG1 SERIES VFD MN040010EN—September 2016 www.eaton.com...
Page 72
Eaton EtherNet/IP products. The imported tags will match the layouts for the I/O assemblies chosen and displayed later in this section and can be used directly in your programs. This tool and a user manual can be downloaded from the Eaton website at the following link: www.eaton.com/software...
1 byte length indicator) REAL 32-bit floating point value SHORT_STRING Character string (1 byte per character, 1 byte length indicator) Table 72. CNnsorucoed daoa oypes Type Code Description Abbreviated array type encoding Formal structure type encoding POWERXL DG1 SERIES VFD MN040010EN—September 2016 www.eaton.com...
Product code UINT 0x3000 Revision STRUCT of Major revision USINT Minor revision USINT Status WORD 0x34–Default Serial number UDINT Product name SHORT_STRING PowerXL DG1 Insoance services Get_attributes_all Reset Reset type 0 & 1 Get_attribute_single POWERXL DG1 SERIES VFD MN040010EN—September 2016 www.eaton.com...
Open format rejects UINT Open resource rejects UINT Open other rejects UINT Close requests UINT Close format requests UINT Close other requests UINT Connection timeouts UINT Insoance services Get_attributes_all Get_attribute_single Forward_close Unconnected_send Forward_open POWERXL DG1 SERIES VFD MN040010EN—September 2016 www.eaton.com...
Set service is applicable only in Static IP addressing Mode. Attribute configuration control supports only value 0 Noee: (device is using configuration values that are stored in non-volatile memory). Attribute host name is used just for information purposes. POWERXL DG1 SERIES VFD MN040010EN—September 2016 www.eaton.com...
Forced interface speed UINT Interface type USINT Interface state USINT Admin state USINT Get/Set 01 (Other value write is invalid) Interface label Short String ASCII code of “PowerXL DG1” Insoance services Get_attribute_all Set_attribute_single Get_attribute_single POWERXL DG1 SERIES VFD MN040010EN—September 2016 www.eaton.com...
Page 79
Array of UINT 04 00 Maximum ID class attribute USINT 07 00 Maximum ID instance attribute USINT 04 00 Class services Get_attribute_single Insoance aooribuoes Data ARRAY of BYTES Get/Set Insoance services Set_attribute_single Get_attribute_single POWERXL DG1 SERIES VFD MN040010EN—September 2016 www.eaton.com...
Squirrel cage induction motor (7) Second rated current UINT-NV Get/Set 120,1,5000 Second rated voltage UINT-NV Get/Set 380,180,690 Second rated frequency UINT-NV Get/Set 50,30,400 Pole count UINT 4,1,8 Second base speed UINT-NV Get/Set 1440,300,20000 Insoance services Get_attribute_single Set_attribute_single POWERXL DG1 SERIES VFD MN040010EN—September 2016 www.eaton.com...
10 sec 0-60sec Insoance Services Get_attribute_single Set_attribute_single Reset (Type 0) Type 0 See Appendix C for list of Fault Codes. Noee: When both Run (Run1 & Run2) attributes set, then no action. POWERXL DG1 SERIES VFD MN040010EN—September 2016 www.eaton.com...
UINT-NV Get/Set 468,1,46875 Decel time 2 UINT-NV Get/Set 468,1,46875 Time scale SINT-NV Get/Set 6,0,127 Insoance services Defaulo Get_attribute_single Set_attribute_single Final Accel Time = Accel Time 1 x (2 to power Time Scale). Noee: POWERXL DG1 SERIES VFD MN040010EN—September 2016 www.eaton.com...
Insoance aooribuoes Varies for different objects Insoance services Get_attribute_single Set_attribute_single All the drive parameters given in the application Noee: manual are accessible using the vendor parameter object. See Appendix A for instance values. POWERXL DG1 SERIES VFD MN040010EN—September 2016 www.eaton.com...
Page 85
In Freq. control—Process Ref is Process Data IN8 (Analog Output 1, reading the actual output current.). In Torque control—Process Ref is Process Data IN1 (Torque Reference) Based on selection of AO, process reference value will be sent on AO out. POWERXL DG1 SERIES VFD MN040010EN—September 2016 www.eaton.com...
Speed Reference commands for Instances 20, 21, 23, and 101 are set up to send the RPM value. This value is sent based off the Motor Nameplate setting provided in the drive. This would be the direct RPM value written. POWERXL DG1 SERIES VFD MN040010EN—September 2016 www.eaton.com...
This is the reference1 to the frequency converter. Used normally as Speed reference. The allowed scaling is 0 to 10000. In the application, the value is scaled in percentage of the frequency area between set minimum and maximum frequency. (0 = 0.00%–10000 = 100.00%). POWERXL DG1 SERIES VFD MN040010EN—September 2016 www.eaton.com...
(0 = 0.00%–10000 = 100.00%). Noee: See info on Assembly 101 for varying values in the Process Data Out 1 and Process Data Out 2 Bytes. See Appendix B on default Process Data info. POWERXL DG1 SERIES VFD MN040010EN—September 2016 www.eaton.com...
(0 = 0.00%–0000 = 100.00%). The RPM Speed Actual is the actual speed of the motor. The unit is RPM. Noee: See Appendix B for Process Data Value defaults. POWERXL DG1 SERIES VFD MN040010EN—September 2016 www.eaton.com...
This is the actual value from the frequency converter. The value is between 0 and 10000. In the application, the value is scaled in percentage of frequency area between set minimum and maximum frequency. (0 = 0.00%–10000 = 100.00%). POWERXL DG1 SERIES VFD MN040010EN—September 2016 www.eaton.com...
Your G-Max HVAC drive is equipped with BACnet support as 76800, 115200 standard. BACnet MS/TP connections The control board is located inside the control unit of the DG1 Series Drive. Figure 28. Principal example diagram POWERXL DG1 SERIES VFD MN040010EN—September 2016 www.eaton.com...
4. Then connect the cable to its appropriate terminals on See also step 8 below. G-Max drive standard terminal block, terminals A and B (A = negative, B = positive). See illustration below. POWERXL DG1 SERIES VFD MN040010EN—September 2016 www.eaton.com...
See illustration below. See also step 6 above. We recommend that the first device on the bus terminated is the Master device. BACnet MS/TP bus termination Figure 34. BACneo bus oerminaoiNn POWERXL DG1 SERIES VFD MN040010EN—September 2016 www.eaton.com...
1. First ensure that the right fieldbus protocol is selected. Navigate: Main Menu → Parameter → Communication → Modbus RTU/BACnet MS/TP → RS-485 Comm Set → Edit → (Choose Protocol as BACnet MS/TP) POWERXL DG1 SERIES VFD MN040010EN—September 2016 www.eaton.com...
Communication time-out BACnet board initiates a communication error if the board is a “sole master” in the network for a time defined with this parameter. POWERXL DG1 SERIES VFD MN040010EN—September 2016 www.eaton.com...
Page 98
600. Default value of password is empty string; this is a writable property with max length of 20, it always returns ***** on read. Same password will be used for Reinitialize Device Service and Device communication Control service. POWERXL DG1 SERIES VFD MN040010EN—September 2016 www.eaton.com...
OFF/ON BV 23 Digital output 4 Relay 3 output OFF/ON For Present Value Access Types, R = Read-only, Noee: W = Writeable, C = Commandable. Commandable values support priority arrays and relinquish defaults. POWERXL DG1 SERIES VFD MN040010EN—September 2016 www.eaton.com...
Analog output 1 Volts AV26 Analog output 2 Analog output 2 Volts Noee: For Present Value Access Types, R = Read-only, W = Writeable, C = Commandable. Commandable values support priority arrays and relinquish defaults. POWERXL DG1 SERIES VFD MN040010EN—September 2016 www.eaton.com...
Page 101
BACnet MS/TP—On-Board communication Fault tracing POWERXL DG1 SERIES VFD MN040010EN—September 2016 www.eaton.com...
Line length depends on different transmission speeds. Table 102. Line length Baud rate (kbit/s) 19.2 93.75 187.5 1500 3000–12000 Length line A [m] 1200 1200 1200 1000 Length line B [m] 1200 1200 1200 — — POWERXL DG1 SERIES VFD MN040010EN—September 2016 www.eaton.com...
BF (RED, the middle one) SF (RED, the right one) Fault condition Blinking Blinking Blinking Board Initialization Everything OK No communication blinking Communication, but not in data exchange No communication and system fault Communication and system fault POWERXL DG1 SERIES VFD MN040010EN—September 2016 www.eaton.com...
VP, +5V, (Voltage- Plus, Isolated 5V from RS-485 side) No use (or P24, Plus 24V Output Voltage) RXD/TXD-N, Negative of Receive or Transmit signal No use (or CNTR_N, Control-N) Use 5.0 mm connector and pin assignment. POWERXL DG1 SERIES VFD MN040010EN—September 2016 www.eaton.com...
Conductor area >0.34 mm >0.22 mm Table 106. Recommended cable Cable Description Part Number Belden PROFIBUS Data Cable 3079A Olflex PROFIBUS Cable 21702xx Siemens SINEC L2 LAN cable for PROFIBUS 6XV1830 = 0AH0 POWERXL DG1 SERIES VFD MN040010EN—September 2016 www.eaton.com...
13:53 13:53 Menu Reverse Reverse Down Arrow key to set Parameters, Right/OK key Right/OK key B7.1.3: Protocol Status or down key to desired B7.1.1: Board Status parameter B7.1.2: Firmware Version 13:53 Menu Reverse POWERXL DG1 SERIES VFD MN040010EN—September 2016 www.eaton.com...
X will depend on the slot the drive is in, Slot A = 7 , Slot B = 14. The parameters of every device must be set before connecting to the bus. Especially the parameters “Slave Address” must be same as set in Master. POWERXL DG1 SERIES VFD MN040010EN—September 2016 www.eaton.com...
The desired PPO Modules define the amount of data that is transferred. Once drive is set in Bypass mode, it will give the ability to set the desired PPO module. POWERXL DG1 SERIES VFD MN040010EN—September 2016 www.eaton.com...
(P1.1) and 10,000 or %100.00 as Maximum Frequency (P1.2). This value has 2 decimal places in it. Process data in 1 to 8 Process Data In values 1 to 8 can be used in applications for various purposes. POWERXL DG1 SERIES VFD MN040010EN—September 2016 www.eaton.com...
— — — — — — — — RUNEN BYS AREF WARN FLT DIR RUN RDY Information about the status of the device and messages is indicated in the Status Word. The Status Word is composed of 16 bits that have the following meanings. POWERXL DG1 SERIES VFD MN040010EN—September 2016 www.eaton.com...
DP . PROFIdrive consists of a general part and a bus specific part. The following properties are defined in the general part. Base Model • Parameter model • Application Model • POWERXL DG1 SERIES VFD MN040010EN—September 2016 www.eaton.com...
PowerXL PROFIBUS optional card support below application class 1. Table 116. Application class Application class Interface Function Standard Drive (e.g., n-set point Cyclic I/O data interface pumps, fans, agitators) Figure 40. Application class POWERXL DG1 SERIES VFD MN040010EN—September 2016 www.eaton.com...
The drive then runs-up to the set point. Disable Operation (Stop) The drive coasts down to a standstill (ramp-function generator to 0 or tracking) and goes into the “Switched on” condition (refer to control word 1, bit 0). POWERXL DG1 SERIES VFD MN040010EN—September 2016 www.eaton.com...
Page 114
1) speed control. “old” process data is kept, 2) positioning. DO I/O Data are set to 0. Device Specific Device Specific Device Specific Device Specific Device Specific Device Specific Device Specific Device Specific Device Specific Device Specific POWERXL DG1 SERIES VFD MN040010EN—September 2016 www.eaton.com...
Motor Off with Coast 0x057F Run Command with RFG and with Set point At Jog Speed Motor ON at Jog Speed 0x0477 Disable Operation Motor Off with Coast 0x0480 Fault Reset bit Fault should get reset POWERXL DG1 SERIES VFD MN040010EN—September 2016 www.eaton.com...
Actual value ≥ comparison value (set point) which may be set via the parameter number. f Or n Not Reached Device Specific Device Specific Device Specific Device Specific Device Specific Device Specific Device Specific Device Specific Device Specific Device Specific POWERXL DG1 SERIES VFD MN040010EN—September 2016 www.eaton.com...
N2 data type N2 data type N2 data type Frequency in decimal percentage decimal 4000 16384 3000 12288 2000 8192 1000 4096 F000 61440 –25 E000 57344 –50 D000 53248 –75 C000 49152 –100 POWERXL DG1 SERIES VFD MN040010EN—September 2016 www.eaton.com...
All stop-reactions caused by faults (Fault with Ramp • stop, Fault with Quick stop, Fault with Coast stop) for the general state machine to switch to state S1 (Switching on Inhibited) or S2 (Ready For switching) POWERXL DG1 SERIES VFD MN040010EN—September 2016 www.eaton.com...
Table 121. PROFIBUS option Card Signal Significance Abbreviation Length Control word 1 STW1 Status word 1 ZSW1 Speed set point A NSOLL_A Speed actual value A NIST_A POWERXL DG1 SERIES VFD MN040010EN—September 2016 www.eaton.com...
Axis-No. / DO-ID mirrored No. of parameters = n 1st Parameter Value (s) (only after Format values or error values No.of values request “Request”) nth Parameter values 4 +... + (Format_n × Qty_n) POWERXL DG1 SERIES VFD MN040010EN—September 2016 www.eaton.com...
PROFIBUS-DP external communication cards Coding Coding of the fields in parameter request/parameter response of base model parameter access. The Eaton PowerXL Profibus board support only single parameter and single element. Max No. of Parameters = 1 Max No. of Elements = 1 Max No.
Page 122
Limitation because of 240 Bytes Data block size (compatible with former PROFIdrive version 3.1.2). 0xEB…0xFF Reserved Error Number Unsigned 16 0x0000… Error numbers The more significant byte is reserved. 0x00FF Generic station description (GSD) file Please refer GSD file “EATN0EF5.gsd” POWERXL DG1 SERIES VFD MN040010EN—September 2016 www.eaton.com...
CANopen cable To meet the ISO 11898 standard, cables to be used with The Eaton PowerXL DG1 series can be connected to the CANbus lines should have a nominal impedance of 120 CANopen system using a fieldbus board. Through this board ohms, a line delay of 5 ns/m.
CANopen external communication cards CANopen bus termination Figure 42. CANopen bus termination CANopen POWERXL DG1 SERIES VFD MN040010EN—September 2016 www.eaton.com...
Table 134. CANopen module status—Run LED (D2-Green LED) Illumination Pattern Meaning Description Blinking PREOPERATIONAL The device is in state PREOPERATIONAL Single flash STOPPED The device is in state STOPPED OPERATIONAL The device is in state OPERATIONAL POWERXL DG1 SERIES VFD MN040010EN—September 2016 www.eaton.com...
Optional Card Menu. Option card parameters Once the card is detected, the following parameters can be set on keypad for CANopen. Figure 44. CANopen parameters POWERXL DG1 SERIES VFD MN040010EN—September 2016 www.eaton.com...
The usage of devices in a communication network requires configuration of the device parameters and communication facilities. CANopen defines the required standard way to access these parameters via the object directory. Please refer to the EDS file “PowerXL_CANopen_vx.x.eds. ” POWERXL DG1 SERIES VFD MN040010EN—September 2016 www.eaton.com...
The functional part determines the object priority. This kind of identification field allows communication between a master and 127 slaves. Broadcasting is indicated by a module-ID of zero. Function codes are determined with object dictionaries in device profiles. POWERXL DG1 SERIES VFD MN040010EN—September 2016 www.eaton.com...
After the node has received the communication reset, it will enter into the “Pre-Operational” state. Table 142. Reset communication message CAN ID LENGTH DATA 0 DATA 1 DATA 2 DATA 3 DATA 4 DATA 5 DATA 6 DATA 7 0x82 NODE ID POWERXL DG1 SERIES VFD MN040010EN—September 2016 www.eaton.com...
The modes INIT, STOP , RUN and FAULT correspond to the actual mode of the drive. SW = StatusWord CW = ControlWord Figure 46. Internal state machine POWERXL DG1 SERIES VFD MN040010EN—September 2016 www.eaton.com...
Rising Edge resets active faults. Reserved Not Used Reserved Not Used Reserved Not Used Manufacturer Specific Not Used Manufacturer Specific Not Used Manufacturer Specific Not Used Manufacturer Specific Not Used Manufacturer Specific Not Used POWERXL DG1 SERIES VFD MN040010EN—September 2016 www.eaton.com...
This signed value is the motor actual rpm speed. A negative value will indicate that the motor is running in the clockwise rotation. By default, this is mapped into the TxPDO1. Range: –32678 to 32767 POWERXL DG1 SERIES VFD MN040010EN—September 2016 www.eaton.com...
Motor Speed. Scaled with percentage function _torque_percentage Calculated torque. Scaled in 0.0%–100% (0–1000) _current_percentage Measured motor current. (1 = 0.01 A) fault_code Shows the drive fault code (= 0, if no fault active) POWERXL DG1 SERIES VFD MN040010EN—September 2016 www.eaton.com...
0 being 0 rpm and 10000 indicating 100.00% speed value. A negative value will indicate the inverted direction. Process data in The Process Data In values are based off the application selected. See Appendix B to reference the current Process Data In values assigned. POWERXL DG1 SERIES VFD MN040010EN—September 2016 www.eaton.com...
Parameter group in the application parameters. These 10000 value, which indicates 0 to 100.00% speed actual. 8 values can be set to any available Modbus ID value listed. See Appendix B to reference the default Process Data Out values assigned. POWERXL DG1 SERIES VFD MN040010EN—September 2016 www.eaton.com...
Number of mapped objects Unsigned8 60400020-controlword Unsigned32 60420010-vl target velocity Integer16 1601 5633 Receive PDO 2 mappings Number of mapped objects Unsigned8 60520010-vl nominal percentage Integer16 60490120-vl velocity deceleration-delta speed Unsigned32 60490210-vl velocity deceleration-delta time Integer16 POWERXL DG1 SERIES VFD MN040010EN—September 2016 www.eaton.com...
Page 140
Highest sub index Unsigned8 COB ID Unsigned32 Transmission type Unsigned8 Inhibit Time Unsigned16 Event timer Unsigned16 1A00 6656 Transmit PDO 1 mappings Number of mapped objects Unsigned8 60410010-statusword Unsigned16 60440010-vl control effort Unsigned16 POWERXL DG1 SERIES VFD MN040010EN—September 2016 www.eaton.com...
If write is success, index 2002 ID and value will will get value 0xFFFF (Dec 65535). be cleared and new write is possible. If write fails, ID will clamp to 0xFFFF and value zero. POWERXL DG1 SERIES VFD MN040010EN—September 2016 www.eaton.com...
FB process data out 3 Integer16 201D 8221 FB process data out 4 Integer16 201E 8222 FB process data out 5 Integer16 201F 8223 FB process data out 6 Integer16 2063 8291 Fault code Integer16 POWERXL DG1 SERIES VFD MN040010EN—September 2016 www.eaton.com...
Page 143
Modbus ID value listed. See Appendix B to reference the default Process Data Out values assigned. Fault code The Fault Code is an indication of the current fault code; the default value will be 0. POWERXL DG1 SERIES VFD MN040010EN—September 2016 www.eaton.com...
Nodes can also be removed or inserted into the network without powering it down. Figure 48. Trunk lines or drop lines Hardware specification Figure 49. DeviceNet hardware POWERXL DG1 SERIES VFD MN040010EN—September 2016 www.eaton.com...
A specific Communication Faulted device. The device has detected a Network Access error and is in the and Received an and Green Communication Faulted state. The device has subsequently received and accepted an Identify Communication Identify Comm Fault Faulted Request—Long Protocol message. Request—Long Protocol POWERXL DG1 SERIES VFD MN040010EN—September 2016 www.eaton.com...
Optional Card Menu. Option card parameters Once the card is detected, the following parameters can be set on keypad for DeviceNet. Figure 50. DeviceNet parameters POWERXL DG1 SERIES VFD MN040010EN—September 2016 www.eaton.com...
8-byte data protocol. Before messages are sent, the master and slave need to be configured. In the configuration, it contains the source and destination object attribute addresses for the master and slave. POWERXL DG1 SERIES VFD MN040010EN—September 2016 www.eaton.com...
In Freq. control—Process Ref is Process Data IN8 (Analog Output, reading the actual output current.). In Torque control—Process Ref is Process Data IN1 (Torque Reference) Based on selection of AO, process reference value will be sent on AO out. POWERXL DG1 SERIES VFD MN040010EN—September 2016 www.eaton.com...
Speed Reference commands for Instances 20, 21, 23, and 101 are set up to send the RPM value. This value is sent based off the Motor Nameplate setting provided in the drive. This would be the direct RPM value written. POWERXL DG1 SERIES VFD MN040010EN—September 2016 www.eaton.com...
This is the reference1 to the frequency converter. Used normally as Speed reference. The allowed scaling is 0 to 10000. In the application, the value is scaled in percentage of the frequency area between set minimum and maximum frequency. (0 = 0.00%–10000 = 100.00%). POWERXL DG1 SERIES VFD MN040010EN—September 2016 www.eaton.com...
(0 = 0.00%–10000 = 100.00%). otee: See info on Assembly 101 for varying values in the Process Data Out 1 and Process Data Out 2 Bytes. See Appendix B on default Process Data info. POWERXL DG1 SERIES VFD MN040010EN—September 2016 www.eaton.com...
In the application, the value is scaled in percentage of frequency area between set minimum and maximum frequency. (0 = 0.00%–0000 = 100.00%). The RPM Speed Actual is the actual speed of the motor. The unit is RPM. See Appendix B for Process Data Value defaults. otee: POWERXL DG1 SERIES VFD MN040010EN—September 2016 www.eaton.com...
This is the actual value from the frequency converter. The value is between 0 and 10000. In the application, the value is scaled in percentage of frequency area between set minimum and maximum frequency. (0 = 0.00%–10000 = 100.00%). otee: See Appendix B for Process Data Value defaults. POWERXL DG1 SERIES VFD MN040010EN—September 2016 www.eaton.com...
CIP object for drive device 0x29 Control supervisor object CIP object for drive device 0x2A AC/DC drive object CIP object for drive device 0xA0~0xBB Vendor parameters object Vendor specific 0x96 Base device information object Vendor specific POWERXL DG1 SERIES VFD MN040010EN—September 2016 www.eaton.com...
Bit string = 8-bits WORD Bit string = 16-bits SHORT_STRING Character string (1 byte per character, 1 byte length indicator) REAL 32-bit floating point value SHORT_STRING Character string (1 byte per character, 1 byte length indicator) POWERXL DG1 SERIES VFD MN040010EN—September 2016 www.eaton.com...
Major Revision USINT Minor Revision USINT As Device Version Status WORD Refer Table 168 Serial Number UDINT Runtime = 0 Product Name SHORT_STRING PowerXL VFD DeviceNET Comm. Card Instance services Service Service Get_attribute_single Reset POWERXL DG1 SERIES VFD MN040010EN—September 2016 www.eaton.com...
Value Description Self-Testing or Unknown At least one faulted I/O connection No I/O connections established At least one I/O connection in run mode At least one I/O connection established, all in idle mode POWERXL DG1 SERIES VFD MN040010EN—September 2016 www.eaton.com...
Allocation information STRUCT of: Allocation choice byte BYTE Bit 0 = Explicit Bit 1 = Poll Master’s MAC ID USINT 1 Range 0–63, 255 Modified via Allocate only Instance services Service Get_attribute_single Set_attribute_single POWERXL DG1 SERIES VFD MN040010EN—September 2016 www.eaton.com...
Maximum ID class attribute USINT 07 00 Maximum ID instance attribute USINT 04 00 Class services Service Get_attribute_single Instance attribute Description Data type Access rule Data Array of BYTES Get/Set Instance services Service Set_attribute_single Get_attribute_single POWERXL DG1 SERIES VFD MN040010EN—September 2016 www.eaton.com...
Instance 1 Motor type and Pole count are also part of instance 2 and instance 3. Refer the application manual for the default values of the motor data attribute parameters. POWERXL DG1 SERIES VFD MN040010EN—September 2016 www.eaton.com...
This attribute to have 3 values as • 0 = No Action (Hold Last State) in Idle Communication mode • 1 = Stop Motor in Idle Communication mode • 2 = Fault Motor in Idle Communication mode • POWERXL DG1 SERIES VFD MN040010EN—September 2016 www.eaton.com...
SINT Get/Set Instance services Service Get_attribute_single Set_attribute_single Note Varies based off drive parameter settings. AC/DC drive object otee: Refer to the PowerXL Application manual for the default values of the parameters. POWERXL DG1 SERIES VFD MN040010EN—September 2016 www.eaton.com...
Access rule Remarks/Default Revision UINT Max Instance UINT Number of Instances UINT Varies for different objects Class services Service Get_attribute_single Instance attribute Description Access rule Varies for different objects Instance services Service Get_attribute_single Set_attribute_single POWERXL DG1 SERIES VFD MN040010EN—September 2016 www.eaton.com...
“PowerXL DG1” Firmware revision Struct of: Major revision USINT Minor revision USINT Hardware version USINT 0xXX Product code UINT 0x3000 Serial number UDINT Runtime = Read from the board Instance services Service Get_attribute_single POWERXL DG1 SERIES VFD MN040010EN—September 2016 www.eaton.com...
PID1 Output 2133 PID1 Status 2150 PID2 Set Point 2864 PID2 Feedback 2167 PID2 Error Value 2124 PID2 Output 2133 PID2 Status 1911 Running Motors PT100 Temperture Latest Fault Code RTC Battery Status POWERXL DG1 SERIES VFD MN040010EN—September 2016 www.eaton.com...
Page 171
AI1 Filter Time P2.2.6 AI1 Signal Invert P2.2.7 1711 AI1 Joystick Hyst P2.2.8 1720 AI1 Sleep Limit P2.2.9 1721 AI1 Sleep Delay P2.2.10 1712 AI1 Joystick Offset P2.3.1 AI2 Mode P2.3.2 AI2 Signal Range POWERXL DG1 SERIES VFD MN040010EN—September 2016 www.eaton.com...
Page 172
P3.32 Jog Enable P3.33 3104 Start Timer 1 P3.34 3104 Start Timer 2 P3.35 3104 Start Timer 3 P3.36 AI Ref Source Select P3.37 1910 Motor Interlock 1 P3.38 1910 Motor Interlock 2 POWERXL DG1 SERIES VFD MN040010EN—September 2016 www.eaton.com...
Page 173
1202 Torque Limit Supv P5.12 1102 Torque Limit Supv Val P5.13 1200 Ref Limit Supv P5.14 1100 Ref Limit Supv Val P5.15 2205 Ext Brake Off Delay P5.16 2205 Ext Brake On Delay POWERXL DG1 SERIES VFD MN040010EN—September 2016 www.eaton.com...
Page 174
Logic Operation Input A P6.3 2001 Logic Operation Input B P7.1 Remote 2 Control Place P7.2 Remote 2 Reference P7.3 Keypad Reference P7.4 Keypad Direction P7.5 Keypad Stop P7.6 Jog Reference P7.7 Motor Pot Ramp Time POWERXL DG1 SERIES VFD MN040010EN—September 2016 www.eaton.com...
Page 175
Speed Error Band Stop Frequency P8.20 1593 2400 Speed Control Kp P8.21 1594 2401 Speed Control Ti P8.22 1595 2400 Speed Control Kp At Field Weakening P8.23 1596 2400 Speed Control Kp Below F0 POWERXL DG1 SERIES VFD MN040010EN—September 2016 www.eaton.com...
Page 176
1012 Motor Thermal F0 Current P9.10 1011 Motor Thermal Time P9.11 28963 Stall Protection P9.12 1010 Stall Current Limit P9.13 1010 Stall Time Limit P9.14 1010 Stall Frequency Limit P9.15 28979 Underload Protection POWERXL DG1 SERIES VFD MN040010EN—September 2016 www.eaton.com...
Page 177
PID Feedback AI Loss Attempts P9.56 2427 STO Fault Response P9.57 2483 Fault Reset Start P10.1 1294 2100 PID1 Control Gain P10.2 1295 2101 PID1 Control ITime P10.3 1296 2102 PID1 Control DTime POWERXL DG1 SERIES VFD MN040010EN—September 2016 www.eaton.com...
Page 178
PID1 Feedforward 2 Source P10.46 1344 2816 PID1 Feedforward 2 Min P10.47 1345 2817 PID1 Feedforward 2 Max P10.48 1352 2830 PID1 Set Point 1 Comp Enable P10.49 1353 2831 PID1 Set Point 1 Comp Max POWERXL DG1 SERIES VFD MN040010EN—September 2016 www.eaton.com...
Page 180
Smoke Purge Frequency P15.7 2443 Fire Mode Test Enable P16.1 Motor Nom Current 2 P16.2 Motor Nom Speed 2 P16.3 Motor PF 2 P16.4 Motor Nom Volt 2 P16.5 Motor Nom Freq 2 POWERXL DG1 SERIES VFD MN040010EN—September 2016 www.eaton.com...
Page 182
Auto-Change Interval P18.4.5 1902 Auto-Change Freq Limit P18.4.6 1903 Auto-Change Pump Limit P18.4.7 2439 Pipe Fill Aux Pump Select P18.4.8 2440 Pipe Fill Aux Pump Run Time P18.4.9 2441 Pipe Fill Aux Pump Operation POWERXL DG1 SERIES VFD MN040010EN—September 2016 www.eaton.com...
Page 183
Interval 3 To Day P19.15 3124 Interval 3 Channel P19.16 Interval 4 On Time P19.17 Interval 4 Off Time P19.18 3122 Interval 4 From Day P19.19 3123 Interval 4 To Day P19.20 3124 Interval 4 Channel POWERXL DG1 SERIES VFD MN040010EN—September 2016 www.eaton.com...
Motor Current Motor Torque Motor Power Motor Voltage DC-link Voltage Unit Temperature Motor Temperature Keypad Torque Ref Keypad Reference 1307 2170 PID1 Keypad Set Point 1 1309 2179 PID1 Keypad Set Point 2 POWERXL DG1 SERIES VFD MN040010EN—September 2016 www.eaton.com...
The monitoring values and drive parameters can be selected using the ID number. Default selections are shown in the table above. Reference Appendix A for Modbus IDs that can be set via the keypad P20.1 FB Process Data Out group. POWERXL DG1 SERIES VFD MN040010EN—September 2016 www.eaton.com...
Process data IN7 Actual value 2 to PID2 controller UINT 0.01% Process data IN8 Analog output UINT 0.01% — To change the Application, go into the P21.1.2 Application to adjust the desired All-in-One application. POWERXL DG1 SERIES VFD MN040010EN—September 2016 www.eaton.com...
Page 192
Digital Inputs D1 to D3 they would change P20.1.8 from an 8 to a 12. For a complete list of parameters please refer to Communication Application Guide MN040010EN which can be found on the www.eaton.com/ drives web site.
Possible power wiring error detected Fault 0x5400h 37121 Current measure fault Fault 0x2100h 9217 Control board overtemp Fault 0x4300h 16914 Internal-ctrl supply Fault 0x5112h 20737 Too many speed search restarts Fault 0xA018h 33809 POWERXL DG1 SERIES VFD MN040010EN—September 2016 www.eaton.com...
Page 194
Configurable—Faults that are specified as “Configurable” have “Fault configuration parameter” associated with them. This configuration parameter can be configured as using keypad (menu P9. Protections) or using PowerXL EIP vendor specific object. POWERXL DG1 SERIES VFD MN040010EN—September 2016 www.eaton.com...
Page 195
Eaton is dedicated to ensuring that reliable, efficient and safe power is available when it’s needed most. With unparalleled knowledge of electrical power management across industries, experts at Eaton deliver customized, integrated solutions to solve our customers’ most critical challenges.
Need help?
Do you have a question about the PowerXL DG1 Series and is the answer not in the manual?
Questions and answers