Pa3_39 Speed Command Fine Adjustment Gain; Pa3_40 Torque Command Fine Adjustment Gain; Pa3_41~44 Address Free Assignment 1 To 4 (For Modbus) - Fuji Electric Alpha7 VV User Manual

Hide thumbs Also See for Alpha7 VV:
Table of Contents

Advertisement

PA3_39 Speed command fine adjustment gain

No.
39
Speed command fine adjustment gain
The gain is finely adjusted in relation to the speed command.
In an X-Y table or similar where two or more servomotor axes are interpolated with analog speed
commands, you can make the D/A scale of the host unit match the A/D scale of the servo amplifier.
Interpolation accuracy is improved with this.
[Example]
If the VREF voltage is 5 [V] and PA3_39 is 1.0100, the speed command inside the servo amplifier
is 5.05 [V] (5 x 1.0100).

PA3_40 Torque command fine adjustment gain

No.
40
Torque command fine adjustment gain
The gain can be finely adjusted in relation to the torque command.
The function is similar to that of PA3_39 (speed command fine adjustment gain).
[Example]
If TREF voltage is 3 [V] and PA3_40 is 1.0100, the torque command inside the servo amplifier is
3.03 [V] (3 × 1.0100).
PA3_41~44 Address free assignment 1 to 4 (for Modbus)
No.
Address free assignment 1
41
(for Modbus)
Address free assignment 2
42
(for Modbus)
Address free assignment 3
43
(for Modbus)
Address free assignment 4
44
(for Modbus)
Name
0.8000 to 1.2000
Name
Name
Input Terminal Function Setting Parameters
CHAPTER 4 PARAMETER
Setting range
Default value
Setting range
Default value
0.8000 to 1.2000
Setting range
Default value
00000000 to
00000000
99999999
00000000 to
00000000
99999999
00000000 to
00000000
99999999
00000000 to
00000000
99999999
Change
1.0000
Always
Change
1.0000
Always
Change
Power
Power
Power
Power
4-105
4