Command Positioning Completion - Fuji Electric Alpha7 VV User Manual

Hide thumbs Also See for Alpha7 VV:
Table of Contents

Advertisement

Command positioning completion: Sequence output signal (Reference value 82)
The signal is turned on after the command value inside the servo amplifier is completed.
 Function
The signal changes from ON to OFF when starting manual operation, automatic operation, homing,
or interrupt positioning, and from OFF to ON when the internal command becomes zero. However,
the OFF status will continue if still running, even if the command is zero such as while the
automatic operation continue stop timer is still counting up for example. When continuation of
operation is disabled due to alarm detection, emergency stop detection or OT detection, this signal
is immediately turned on.
Speed
Command
Start positioning
Command positioning
completion
In-position
If the command positioning completion signal is assigned to an output signal, the condition for the next
start signal is activation of the command positioning completion signal. Refer to the timing chart below.
(Example : Positioning continuation)
Speed
Start positioning
Command
positioning
completion
In-position
[INP]
If a motion to the current position is started, the servomotor does not start but the in-position signal is
turned off for the time specified in PA1_34 (in-position minimum OFF time / single shot ON time).
Motor speed
ON
OFF
OFF
Motor
speed
Command
ON
OFF
ON
OFF
CHAPTER 2 WIRING
Time
ON
ON
Time
Description of I/O Signals
2
2-99