Power-On/Servo Control-Ready [S-Rdy] - Fuji Electric Alpha7 VV User Manual

Hide thumbs Also See for Alpha7 VV:
Table of Contents

Advertisement

 If the keypad does not light up
Appropriate voltage (200 [V]) is not supplied to the control power terminals (L1C and L2C). Check
the source voltage.
In case of three-phase 400 [V], use a transformer to drop to 200 [V] to supply. (400 [V] will
damage the servo amplifier.)
 If the keypad indicates differently
If two characters from the left is "AL. " an alarm is detected. In this case, the display blinks.
If the keypad shows those other than specified above, the servo amplifier is not in the factory
shipment state.
3.3.2

Power-On/Servo Control-Ready [S-RDY]

The servo control ready [S-RDY] signal is issued about 4.5 seconds after the control and main power
supplies are turned on.
The CPU inside the servo amplifier diagnoses itself and, if the result is correct, the signal is issued and
remains turned on until the power is shut down.
The servo ready [S-RDY] signal is not output during free-run or STO operation.
Shutdown
Power supply
[SRDY]
OFF
AL. 8 88
Supply
ON
About 4.5 seconds
CHAPTER 3 OPERATION
Operation Check
3
3-5