5.5.2 One-parameter Tuning Procedure

The following procedure is used for one-parameter tuning.
Operation procedures will vary in accordance with the tuning mode being used.
• When the tuning mode is set to 0 with priority given to stability or when the tuning mode is set to 1 with pri-
ority given to responsiveness, refer to (1) Setting the Tuning Mode to 0 or 1.
• When the tuning mode is set to 2 or 3 for adjustments in positioning, refer to (2) Setting the Tuning Mode to
2 or 3.
One-parameter tuning is performed from the Digital Operator (option) or SigmaWin+.
The operating procedure from the Digital Operator is described here.
For basic operations of the Digital Operator, refer to the
ator (SIEP S800000 55).
(1) Setting the Tuning Mode to 0 or 1
Step
Display after Operation
1
Status Display
2
3
4
Tuning Mode Selection
Select the tuning Mode. Select the tuning mode 0 or 1.
4-1
Tuning Mode = 0: Makes adjustments giving priority to stability.
Tuning Mode = 1: Makes adjustments giving priority to responsiveness.
Type Selection
Select the type according to the machine element to be driven.
If there is noise or the gain does not increase, better results may be obtained by changing the rigid type.
4-2
Type = 1: For belt drive mechanisms.
Type = 2: For ball screw drive mechanisms [Factory setting].
Type = 3: For rigid systems, such as a gear.
5
6
Σ
-V series User's Manual, Operation of Digital Oper-
Keys
Press the
Key to view the main menu for the
utility function mode.
Use the
or
select Fn203.
Press the
Key to display the mass ratio set in
Pn103 at present. To change the setting, move the
cursor with the
value with the
Note:
If the display does not switch and "NO-OP" is dis-
played, take corrective action after checking the items
given in 5.5.1 (1) Before Performing One-parameter
Tuning.
Press the
Key to display the initial setting screen
for one-parameter tuning.
Press the
,
steps 4-1 and 4-2.
Input a servo ON command from the host controller.
The display will change from "BB" to "RUN."
Press the
Key to display the set value.
5.5 One-parameter Tuning (Fn203)
Operation
Key to move through the list,
or
Key and change the set
or
Key.
or
Key and set the items in
5
5-33