4.3.2 MR-J4 series, molded-case circuit breakers, fuses, and magnetic contactors (recommended)

(1) For main circuit power supply
CAUTION
When using a fuse instead of the molded-case circuit breaker, use the one having the specifications given in
this section.
Servo amplifier
MR-J4-10_(1)
MR-J4-20_
MR-J4-20_1
MR-J4-40_
MR-J4-60_/70_/40_1
MR-J4-70_
MR-J4-100_
(3-phase power supply input)
MR-J4-100_
(1-phase power supply input)
MR-J4-200_
MR-J4-350_
MR-J4-500_
MR-J4-700_
MR-J4-11K_
MR-J4-15K_
MR-J4-22K_
MR-J4-60_4
MR-J4-100_4
MR-J4-200_4
MR-J4-350_4
MR-J4-500_4
MR-J4-700_4
MR-J4-11K_4
MR-J4-15K_4
MR-J4-22K_4
Note 1. In order for the servo amplifier to comply with the UL/CSA standard, see the applicable "Servo Amplifier Instruction Manual".
2. Use a magnetic contactor with an operation delay time (interval between current being applied to the coil until closure of
contacts) of 80 ms or less.
3. S-N18 can be used when auxiliary contact is not required.
Select a molded-case circuit breaker with a short shut-off time to prevent smoking
and fire from the servo amplifier.
Always use one molded-case circuit breaker and one magnetic contactor with one
servo amplifier.
Molded-case circuit breakers, fuses, and magnetic contactors
Molded-case circuit breaker (Note 1)
Frame, rated current
Power factor improving
Power factor improving
reactor is not used
30 A frame 5 A
30 A frame 10 A
30 A frame 10 A
30 A frame 15 A
30 A frame 15 A
30 A frame 20 A
30 A frame 30 A
50 A frame 50 A
100 A frame 75 A
100 A frame 100 A
125 A frame 125 A
225 A frame 175 A
30 A frame 5 A
30 A frame 10 A
30 A frame 15 A
30 A frame 20 A
30 A frame 20 A
30 A frame 30 A
50 A frame 50 A
60 A frame 60 A
100 A frame 100 A
Voltage
AC [V]
reactor is used
30 A frame 5 A
30 A frame 10 A
30 A frame 5 A
30 A frame 10 A
30 A frame 15 A
240
30 A frame 20 A
30 A frame 30 A
50 A frame 50 A
100 A frame 60 A
100 A frame 100 A
125 A frame 125 A
225 A frame 175 A
30 A frame 5 A
30 A frame 5 A
30 A frame 10 A
30 A frame 15 A
30 A frame 20 A
480
30 A frame 30 A
50 A frame 50 A
60 A frame 60 A
100 A frame 100 A
7 - 24
Fuse
Current
Voltage
Class
[A]
AC [V]
10
15
15
20
30
T
300
40
70
125
150
200
250
350
10
15
25
35
50
T
600
65
100
150
175
Magnetic
contactor
(Note 2)
S-N10
S-T10
S-N20
(Note 3)
S-T21
S-N20
S-T21
S-N35
S-N50
S-N65
S-N95
S-N10
S-T10
S-N20
(Note 3)
S-T21
S-N20
S-T21
S-N25
S-N35
S-N50

Hide quick links: