Mitsubishi Electric MELSERVO-J3 Series Manual page 125

Hide thumbs Also See for MELSERVO-J3 Series:
Table of Contents

Advertisement

Part 3: Review on Replacement of MR-J3-_B_ with MR-J4-_B_
No.
Name and function
PB25
For manufacturer setting
Do not change this value by any means.
PB26
Gain changing selection
Select the gain changing condition.
0 0 _ x:
Gain changing selection
Under any of the following conditions, the gains change
on the basis of the [Pr. PB29 to PB34] settings.
0: Invalid
1: Control instructions from a controller.
2: Command frequency ([Pr. PB27] setting)
3: Droop pulse value ([Pr. PB27] setting)
4: Servo motor speed ([Pr. PB27] setting)
0 0 x _ :
Gain changing condition
0: Valid when the control instruction from a controller is
ON
Valid at equal to or more than the value set in
[Pr. PB27]
1: Valid when the control instruction from a controller is
OFF
Valid at equal to or less than the value set in
[Pr. PB27]
PB27
Gain changing condition
Used to set the value of gain changing condition
(command frequency, droop pulses, servo motor speed)
selected in [Pr. PB26]. The set value unit changes with
the changing condition item.
PB28
Gain changing time constant
Used to set the time constant at which the gains will
change in response to the conditions set in [Pr. PB26
and PB27].
MR-J3-_B_
Initial
No.
value
0000h
PB25
Function selection B-1
Select enabled/disabled of model adaptive control.
This parameter is supported with software version B4 or
later.
_ _ _ x:
Model adaptive control selection
0: Enabled (model adaptive control)
2: Disabled (PID control)
_ _ x _ :
For manufacturer setting
_ x _ _ :
For manufacturer setting
x _ _ _ :
For manufacturer setting
0000h
PB26
Same setting as MR-J3
Gain switching function
Select the gain switching condition.
Set conditions to enable the gain switching values set in
[Pr. PB29] to [Pr. PB36] and [Pr. PB56] to [Pr. PB60].
_ _ _ x:
Gain switching selection
0: Disabled
1: Control command from controller is enabled
2: Command frequency
3: Droop pulses
4: Servo motor speed
_ _ x _ :
Gain switching condition selection
0: Gain after switching is enabled with gain switching
condition or more
1: Gain after switching is enabled with gain switching
condition or less
_ x _ _ :
Gain switching time constant disabling condition
selection
0: Switching time constant enabled
1: Switching time constant disabled
2: Return time constant disabled
This parameter is used by servo amplifier with software
version B4 or later.
x _ _ _ :
For manufacturer setting
10
PB27
Same setting as MR-J3
Gain switching condition
This is used to set the value of gain switching (command
frequency, droop pulses, and servo motor speed)
selected in [Pr. PB26].
The set value unit differs depending on the switching
condition item.
1
PB28
Same setting as MR-J3
Gain switching time constant
This is used to set the time constant at which the gains
will change in response to the conditions set in
[Pr. PB26] and [Pr. PB27].
3 - 32
MR-J4-_B_
Name and function
Initial
value
0h
0h
0h
0h
0h
0h
0h
0h
10
1

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents