6.6
Molded-case circuit breakers, fuses, magnetic
contactors
When using a fuse instead of the molded-case circuit breaker, use the one having the specifications given in this section.
Precautions
• Select the molded-case circuit breakers specified in this section.
• Wire the molded-case circuit breaker and magnetic contactor as recommended.
Servo amplifier
Molded-case circuit breaker
Frame, rated current
Power factor
improving
reactor is not
used
MR-JET-10_
30 A frame 5 A
MR-JET-20_
MR-JET-40_
30 A frame 10 A
MR-JET-70_
30 A frame 15 A
MR-JET-100_
(3-phase power
supply input)
MR-JET-100_
(1-phase power
supply input)
MR-JET-200_
30 A frame 20 A
MR-JET-300_
30 A frame 30 A
*1 Use a fuse to make the servo amplifier comply with UL/CSA standards. To make the servo amplifier comply with IEC/EN/UL/CSA
standards, refer to "MR-JET Safety Instructions and Precautions for AC Servos (IB(NA)-0300492)" for selection of molded-case circuit
breakers and fuses.
*2 Use a magnetic contactor with an operation delay time (interval between current being applied to the coil until closure of contacts) of 80
ms or less.
*3 Use a molded-case circuit breaker that has operation characteristics equal to or higher than Mitsubishi Electric general-purpose
products.
A motor circuit breaker (Type E Combination motor controller) can also be used instead of a molded-case circuit breaker.
Use the motor circuit breaker (Type E Combination motor controller) with the line side terminal adapter UT-CV3 and the short-
circuit indicator unit UT-TU.
Servo amplifier
Rated input
voltage AC [V]
MR-JET-10_
200 to 240
MR-JET-20_
MR-JET-40_
MR-JET-70_
MR-JET-100_
MR-JET-200_
MR-JET-300_
6 OPTIONS AND PERIPHERAL EQUIPMENT
70

6.6 Molded-case circuit breakers, fuses, magnetic contactors

*1*3
Voltage AC
[V]
Power factor
improving
reactor is used
30 A frame 5 A
240
30 A frame 5 A
30 A frame 10 A
30 A frame 15 A
30 A frame 20 A
30 A frame 30 A
Input phase
Motor circuit breaker (Type E combination motor
controller)
Model
3-phase
MMP-T32
Fuse
Class
Current [A]
Semiconductor
10
15
20
30
40
70
Rated voltage
Rated current
AC [V]
[A]
(heater design)
240
1.6
2.5
4
6.3
8
18
25
Magnetic
*2
contactor
Voltage AC
[V]
700
S-T10
S-T21
SCCR [kA]
50
25