Event name
CIP Safety Target Does Not Exist
Meaning
The target node does not exist.
Source
Depends on where the Sysmac
Studio is connected and the sys-
tem configuration.
Error attrib-
Level
utes
Effects
User program
System-de-
Variable
fined varia-
None
bles
Cause and
Assumed cause
correction
The communications cable is dis-
connected or broken.
The target node entered a state
where it could not accept the
connection.
The timeout value in the commu-
nications setup is too small.
There is excessive noise.
Attached in-
Attached infor-
formation
mation 1:
Attached infor-
mation 2:
Attached infor-
mation 3:
Precautions/
None
Remarks
NX-series Safety Control Unit User's Manual (Z930)
Source details NX Unit
Minor fault
Recovery
Continues.
Operation
Data type
None
Correction
Connect the communication ca-
ble securely.
Check if the target node is in a
state where it can accept the
connection.
Increase the timeout value in the
communications setup and trans-
fer the settings.
Implement noise countermeas-
ures.
IP address of the target node
(example: C0A8FA01 hex = address 192.168.250.1)
General Status defined in CIP specifications
Extended Status defined in CIP specifications
12 Troubleshooting
Event code
80330000 hex
Detection tim-
ing
Automatic re-
Log category
covery when
cause of error
is removed
The Unit continues to operate, but the safe states
are used for the I/O data of the safety connection
where the error was detected.
Name
None
Prevention
Set the system configuration and
setup according to the correc-
tions that are given on the left.
In DEBUG
mode (STOP-
PED), DEBUG
mode (RUN),
or RUN mode
System
12
12 - 41