3 Installation and Wiring
1.6 mm max. (except ground terminals)
2.0 mm max. (ground terminals)
l Using Twisted or Solid Wires
If you use twisted wires or solid wires, use the following table to determine the correct wire specifi-
cations.
Terminals
Classifica-
tion
All termi-
nals except
ground ter-
minals
Ground
terminals
*1. Secure wires to the screwless clamping terminal block. Refer to Securing Wires on page 3 - 13 for how to
secure wires.
*2. With the NX-TB£££1 Terminal Block, use twisted wires to connect the ground terminal. Do not use a
solid wire.
Conductor length (stripping length)
Precautions for Correct Use
• Use cables with suitable wire sizes for the carrying current. There are also restrictions on the
current due to the ambient temperature. Refer to the manuals for the cables and use the ca-
bles correctly for the operating environment.
• For twisted wires, strip the sheath and twist the conductor portion. Do not unravel or bend the
conductor portion of twisted wires or solid wires.
3 - 12
Twisted wires
Current
Unplat-
Plated
capacity
ed
2 A max.
Possible
Possible
Greater
Not pos-
than 2 A
sible
and 4 A or
less
Greater
Possi-
than 4 A
*1
ble
---
Possible
Possible
Unravel wires
8 to 10 mm
2.4 mm max. (except ground terminals)
2.7 mm max. (ground terminals)
Wire type
Solid wire
Unplat-
Plated
ed
Possible
Possible
Possi-
Not pos-
sible
*1
ble
Not pos-
sible
Possi-
Possi-
*2
*2
ble
ble
Bend wires
NX-series Safety Control Unit User's Manual (Z930)
Conductor
Wire size
length (strip-
ping length)
8 to 10 mm
2
0.08 to 1.5 mm
(AWG28 to 16)
9 to 10 mm
2
2.0 mm