7 Checking Operation and Actual Operation
13
Check the operation of function reset.
It is displayed only for Manual Reset.
The Controller checks if the variables assigned to all the output devices are set to TRUE when
detecting that the variable assigned to the reset switch changed from FALSE to TRUE, and
then FALSE again. The test result appears in the dialog shown below. If the devices operate
normally as specified in the expected value settings, select the checkbox stating The device
operates normally and then select OK.
14
Repeat the steps 8 through 13 for all the input devices.
Once the operations for all the input devices are completed, the Online Functional Test Result
Page shown below appears.
7 - 48
NX-series Safety Control Unit User's Manual (Z930)