Event name
Safety Unit Restore Operation Failed
Meaning
The restore operation for a Safety Unit ended in an error.
Source
Depends on where the Sysmac
Studio is connected and the sys-
tem configuration.
Error attrib-
Level
utes
Effects
User program
System-de-
Variable
fined varia-
None
bles
Cause and
Assumed cause
correction
The SD Memory Card was re-
moved during a restore operation
for a Safety Unit.
Data was read from or written to
the SD Memory Card via the
Support Software or an FTP cli-
ent during a restore operation for
a Safety Unit.
Attached in-
None
formation
Precautions/
None
Remarks
l Other Errors
NX-series Safety Control Unit User's Manual (Z930)
Source details NX Unit
Observation
Recovery
Continues.
Operation
Data type
None
Correction
Insert the SD Memory Card that
contains the Safety Unit Restore
File, cycle the power supply and
then perform the restore opera-
tion for a Safety Unit again.
Store the correct Safety Unit Re-
store File to the SD Memory
Card, cycle the power supply and
then perform the restore opera-
tion for a Safety Unit again.
12 Troubleshooting
Event code
352B0000 hex
Detection tim-
ing
---
Log category
---
Name
None
Prevention
Do not remove the SD Memory
Card during the restore operation
for a Safety Unit.
Do not read data from or write
data to the SD Memory Card via
the Support Software or an FTP
client during the restore opera-
tion for a Safety Unit.