Omron NX-SL3300 User Manual page 432

Nx series safety control unit
Hide thumbs Also See for NX-SL3300:
Table of Contents

Advertisement

12 Troubleshooting
Event code
Event name
80300000 hex
Safety Proc-
ess Data
[NX-SL3£££]
Communica-
tions Time-
out
80300001 hex
FSoE Mas-
ter Connec-
[NX-SL5£££]
tion Timeout
80310000 hex
CIP Safety
Originator
[NX-SL5£££]
Connection
Not Estab-
lished Error
80320000 hex
CIP Safety
Originator
[NX-SL5£££]
Connection
Timeout
80330000 hex
CIP Safety
Target Does
[NX-SL5£££]
Not Exist
12 - 20
Meaning
A communications
A setting is not correct. The
timeout occurred in
setting of the safety task peri-
safety process data
od is too short.
communications with
There is excessive noise.
the Safety Control
The Safety CPU Unit or safety
Unit.
slave entered a status where it
could not continue safety proc-
ess data communications.
The process data communica-
tions were not performed cor-
rectly because an error or sta-
tus change occurred in the NX
bus master to which the Unit is
connected.
A communication
A setting is not correct. The
timeout occurred in
setting of the safety task peri-
FSoE communica-
od is too short.
tions with the FSoE
There is excessive noise.
slave.
The Safety CPU Unit or FSoE
slave entered a state where it
could not continue FSoE com-
munications.
The process data communica-
tions were not performed cor-
rectly because an error or sta-
tus change occurred in the NX
bus master to which the Unit is
connected.
CIP safety originator
The target node is different.
connection was not
The target node is not config-
established.
ured.
The target node status is inva-
lid.
A timeout occurred in
The communications cable is
CIP safety originator
disconnected or broken.
connection.
The target node entered a
state where it could not accept
the connection.
The timeout value in the com-
munications setup is too small.
There is excessive noise.
The target node does
The communications cable is
not exist.
disconnected or broken.
The target node entered a
state where it could not accept
the connection.
The timeout value in the com-
munications setup is too small.
There is excessive noise.
M
Assumed cause
a
j
NX-series Safety Control Unit User's Manual (Z930)
Level
I
M
O
Reference
P
n
i
b
rt
f
n
s
o
¡
page
12 - 37
¡
page
12 - 38
¡
page
12 - 39
¡
page
12 - 40
¡
page
12 - 41

Advertisement

Table of Contents
loading

Table of Contents