Precautions for Correct Use
• Do not delete the function block CRC data that is displayed after the function block is export-
ed. It is used for data confirmation when the function block is imported.
You can check the CRC data on the Change Tracking Tab Page or Properties Dialog Box.
• A help file is not included with the user-defined function block file (sfb).
Version Information
You can export user-defined function blocks with Sysmac Studio version 1.12 or higher.
Importing User-defined Function Blocks
You can import the exported user-defined function block to reuse it in another project.
Check during the import of the user defined function that the CRC of
the imported function block is correct. Serious injury may possibly occur
due to loss of required safety functions.
Use the following procedure to import a user-defined function block that was previously exported.
1
Right-click Function Blocks under Programming - POUs in the Multiview Explorer and select
Import from the menu.
The Import Dialog Box is displayed.
When you select the files to import, you can press the Shift Key or Ctrl Key to select more
than one file.
2
Select the .sfb file to import, and then click the Open Button.
The following dialog box is displayed. To import the function block help file, select Yes.