Omron NX-SL3300 User Manual page 483

Nx series safety control unit
Hide thumbs Also See for NX-SL3300:
Table of Contents

Advertisement

Event name
Safety Process Data Communications Not Estab-
lished, Incorrect FSoE Slave Address Error
Meaning
Safety process data communications was not established with the Safety CPU Unit because of an incor-
rect FSoE slave address.
Source
Depends on where the Sysmac
Studio is connected and the sys-
tem configuration.
Error attrib-
Level
utes
Effects
User program
System-de-
Variable
fined varia-
None
bles
Cause and
Assumed cause
correction
The setting of the FSoE slave
address in the safety process da-
ta communications settings is dif-
ferent from the setting in the Unit.
Attached in-
None
formation
Precautions/
None
Remarks
NX-series Safety Control Unit User's Manual (Z930)
Source details NX Unit
Minor fault
Recovery
Continues.
Operation
Data type
None
Correction
Perform the Clear All Memory
operation for the Unit.
12 Troubleshooting
Event code
35230000 hex
Detection tim-
ing
For request to
Log category
establish com-
munications
from Safety
CPU Unit after
removing
cause of error
The Unit stops operating and the I/O data changes
to the safe states.
Name
None
Prevention
If you use a Safety I/O Unit for
which safety process data com-
munications were previously es-
tablished in another system, per-
form the Clear All Memory opera-
tion before you use the Unit.
When safety
process data
communica-
tions are estab-
lished
System
12