Omron NX-SL3300 User Manual page 401

Nx series safety control unit
Hide thumbs Also See for NX-SL3300:
Table of Contents

Advertisement

Processing stage
Processing
Wait for Completion Com-
mand
Processing Completion
Done
Restart
NX-series Safety Control Unit User's Manual (Z930)
Procedure and Display
Seven-segment indicators in the Safety CPU Unit repeat turning ON and OFF in
four at a time.
If processing ended in an error, an error code is shown in the seven-segment
indicators in the Safety CPU Unit.
The safety signature for the settings information transferred to the Safety CPU
Unit is repeatedly shown as a four-digit hexadecimal number in the seven-seg-
ment indicators of the Safety CPU Unit.
(Example: Supposing the safety signature is 0xABCD)
Check the safety signature. If it is correct, press and hold the service switch for
one second or more and release.
Completion processes starts.
Seven-segment indicators in the Safety CPU Unit repeat turning ON and OFF in
four at a time.
If processing ended in an error, an error code is shown in the seven-segment
indicators in the Safety CPU Unit.
The safety signature including the date and time (UTC) is repeatedly shown in
the seven-segment indicators of the Safety CPU Unit.
(Example: Supposing the safety signature is 0xABCD, and the date is 16:21:36
of June 22, 2017 (UTC))
After turning OFF the power supply to the Controller, set the pins 1 to 4 of the
DIP switch on the Safety CPU Unit as follows: 1 to OFF, 2 to OFF, 3 to OFF, and
4 to OFF, and turn ON the power supply to the Controller. The Safety CPU Unit
starts in RUN mode.
10 Safety Unit Restore
10 - 5
10

Advertisement

Table of Contents
loading

Table of Contents