Omron NX-SL3300 User Manual page 441

Nx series safety control unit
Hide thumbs Also See for NX-SL3300:
Table of Contents

Advertisement

Event code
Event name
05220000 hex
Internal Cir-
cuit Error at
Test Output
05230000 hex
Internal Cir-
cuit Error at
Safety Out-
put
65200000 hex
I/O Power
Supply Volt-
age Error
65210000 hex
Output Pow-
er Interrupt
Circuit Error
65220000 hex
External Test
Signal Fail-
ure at Safety
Input
65230000 hex
Discrepancy
Error at
Safety Input
65240000 hex
Overload
Detected at
Test Output
65250000 hex
Stuck-at-
high Detect-
ed at Test
Output
65270000 hex
Short Circuit
Detected at
Safety Out-
put
NX-series Safety Control Unit User's Manual (Z930)
Meaning
A fault was detected
The internal circuit for the test
in the internal circuit
output terminal is faulty.
for the test output ter-
A memory error or signal error
minal.
occurred due to a transient
cause, such as an excessive
noise.
A fault was detected
The internal circuit for the safe-
in the internal circuit
ty output terminal is faulty.
for the safety output
A memory error or signal error
terminal.
occurred due to a transient
cause, such as an excessive
noise.
An incorrect I/O pow-
The input power or output
er supply voltage was
power is not supplied correctly.
detected.
An error was detect-
The wiring is not correct or
ed by the output pow-
there is a fault in the hardware.
er interruption test.
An error was detect-
The positive power supply wire
ed in test pulse evalu-
is in contact with the input sig-
ation of the safety in-
nal line.
put terminals.
The input signal lines are
shorted.
The external device is faulty.
An error was detect-
There is a ground fault or dis-
ed in discrepancy
connection in the input signal
evaluation of safety
line.
input terminals.
The connected device is faulty.
The setting of the discrepancy
time is not correct.
Chattering occurred in the in-
put signal from the external in-
put device, such as a safety
door.
An overcurrent was
There is a ground fault on the
detected at the test
output signal line.
output terminal.
The external device is faulty.
It was detected that
The positive power supply line
the test output termi-
is in contact with the output
nal is stuck ON.
signal line.
The internal circuit is faulty.
A memory error or signal error
occurred due to a transient
cause, such as a software er-
ror or excessive noise.
A ground fault was
There is a ground fault on the
detected on the safe-
output signal line.
ty output terminal.
M
Assumed cause
a
j
12 Troubleshooting
Level
I
M
O
Reference
P
n
i
b
rt
f
n
s
o
¡
page
12 - 78
¡
page
12 - 79
¡
page
12 - 80
¡
page
12 - 81
¡
page
12 - 82
¡
page
12 - 83
page
¡
12 - 84
¡
page
12 - 85
¡
page
12 - 86
12 - 29
12

Advertisement

Table of Contents
loading

Table of Contents