Item
I/O refreshing method
External connection terminals
Indicators
Safety input current
Safety input ON voltage
Safety input OFF voltage/OFF
current
Test output type
Test output rated current
Test output ON residual voltage
Test output leakage current
Dimensions (mm)
Isolation method
Insulation resistance
Dielectric strength
I/O power supply method
Current capacity of I/O power
supply terminals
NX Unit power consumption
Current consumption from I/O
power supply
Weight
Circuit layout
NX-series Safety Control Unit User's Manual (Z930)
Free-Run refreshing
Screwless clamping terminal block (8 terminals)
[TS] indicator, [FS] indicator, [IN] indicator, [IN ERR] indicator
[IN] indicator
[IN ERR] indicator
4.5 mA typical
11 VDC min.
5 VDC max./1 mA max.
Sourcing outputs (PNP)
25 mA max.
1.2 V max. (IOV and all output terminals)
0.1 mA max.
12 × 100 × 71 (W × H × D)
Photocoupler isolation
20 MΩ min. between isolated circuits (at 100 VDC)
510 VAC between isolated circuits for 1 minute at a leakage current of 5
mA max.
Power supplied from the NX bus
No applicable terminals.
Connected to a CPU Unit or a Communication Control Unit
1.10 W max.
Connected to a Communications Coupler Unit
0.70 W max.
20 mA max.
70 g max.
T0 – 1
Terminal block
Si0 – 3
NX bus
I/O power supply +
connector
I/O power supply -
(left)
2 Specifications
Specification
I/O power supply +
I/O power supply -
2
NX bus
connector
(right)
2 - 19