Omron NX-SL3300 User Manual page 248

Nx series safety control unit
Hide thumbs Also See for NX-SL3300:
Table of Contents

Advertisement

6 Programming
3
Check the CRC data, and click the OK Button.
The program is imported and added to the project.
Precautions for Correct Use
After a function block is imported, the Safety CPU Unit will be in an unvalidated state. Always
execute safety validation again.
Additional Information
You can check the CRC data on the Change Tracking Tab Page or Properties Dialog Box.
Version Information
You can import programs with Sysmac Studio version 1.17 or higher.
Exporting User-defined Function Blocks
You can export a user-defined function block to a file (extension .sfb).
You can import the exported user-defined function block to reuse it in another project.
Use the following procedure.
1
Right-click the user-defined function block under Programming - POUs - Function Blocks in
the Multiview Explorer and select Export from the menu.
The Export Dialog Box is displayed.
2
Enter a file name, and then click the Save Button.
A function block file with an .sfb extension is saved.
6 - 32
NX-series Safety Control Unit User's Manual (Z930)