7 Checking Operation and Actual Operation
10
Operate the device as instructed on the screen. Execute a restore test.
The operating instructions for the device to be tested will appear. Operate the device as in-
structed on the screen and specify TRUE for the variable assigned to the input device.
11
Make sure that the device was restored normally.
• Reset Type: Manual
The Controller checks if no change is made to the variables assigned to all the output devi-
ces when detecting that the specified variable is set to TRUE. The test result appears in the
dialog shown below. If the devices operate normally as specified in the expected value set-
tings, select the checkbox stating The device operates normally and then select OK.
7 - 46
NX-series Safety Control Unit User's Manual (Z930)