Omron NX-SL3300 User Manual page 191

Nx series safety control unit
Hide thumbs Also See for NX-SL3300:
Table of Contents

Advertisement

The I/O Assembly Settings (Target) Tab Page consists of the items shown in the following ta-
ble.
Active/Inactive
In/Out
I/O Assembly Name
Data Size [byte]
Description
Go To I/O Map Button
Export Button
The following lists the types of selectable I/O Assembly.
Name
InputAssembly 1
InputAssembly 2
InputAssembly 3
OutputAssembly 1
The activated I/O Assembly is displayed as a port on the I/O map of the originator device to communi-
cate with as shown below. You can use it on a safety program by assigning a variable to the I/O port.
NX-series Safety Control Unit User's Manual (Z930)
Item
Use this box to enable or disable each I/O Assembly. When you ena-
ble the assembly, a port is added to the I/O Map.
Selected: I/O Assembly is enabled.
Not selected: I/O Assembly is disabled.
Shows the data direction of each I/O Assembly.
: In – Data sent to the originator device.
: Out – Data received from the originator device.
The name of each I/O Assembly is displayed. It is same as the port
name displayed on the I/O Map.
The byte size of each I/O Assembly is displayed.
The description of each I/O Assembly is displayed.
Click this button to open the I/O Map Tab Page.
Exports the target device settings as a file (extension .tds).
Assembly num-
ber
768(0x300)
769(0x0301)
770(0x0302)
928(0x03A0)
5 System Configuration and Setup
Description
Data direction
Input – Data sent to the origi-
nator device
Input – Data sent to the origi-
nator device
Input – Data sent to the origi-
nator device
Output – Data received from
the originator device
Size
16 bytes (SAFEBOOL ×
128)
16 bytes (SAFEBOOL ×
128)
8 bytes (SAFEBOOL × 64)
8 bytes (SAFEBOOL × 64)
5 - 19
5

Advertisement

Table of Contents
loading

Table of Contents