Omron NX-SL3300 User Manual page 496

Nx series safety control unit
Hide thumbs Also See for NX-SL3300:
Table of Contents

Advertisement

12 Troubleshooting
Event name
Overload Detected at Test Output
Meaning
An overcurrent was detected at the test output terminal.
Source
Depends on where the Sysmac
Studio is connected and the sys-
tem configuration.
Error attrib-
Level
utes
Effects
User program
System-de-
Variable
fined varia-
None
bles
Cause and
Assumed cause
correction
There is a ground fault on the
output signal line.
The external device is faulty.
Attached in-
Attached information 1: Terminal number
formation
Precautions/
None
Remarks
12 - 84
Source details NX Unit
Minor fault
Recovery
Continues.
Operation
Data type
None
Correction
Check the external wiring.
Replace the external device.
Event code
65240000 hex
Detection tim-
ing
When safety
Log category
input terminal
goes inactive
after cause of
error is re-
moved
The safety input terminal that is the test source of
the test output terminal retains the safe state until
the error is removed.
Name
None
Prevention
Set the parameters and wire the
system considering the correc-
tions that are given on the left.
NX-series Safety Control Unit User's Manual (Z930)