Operating environment Ambient operating tem-
Installation method
Individual Specifications
This section provides the individual specifications of the Safety Output Unit.
l Datasheet Items for Safety Output Unit
The following table gives the meaning of the datasheet items for the Safety Output Units.
Number of safety output points
Internal I/O common
Maximum load current
Rated voltage
Number of safety slave connec-
tions
I/O refreshing method
External connection terminals
Indicators
NX-series Safety Control Unit User's Manual (Z930)
Item
perature
Ambient operating humid-
ity
Atmosphere
Ambient storage tempera-
ture
Altitude
Pollution degree
Noise immunity
Insulation class
Overvoltage category
EMC immunity level
Vibration resistance
Shock resistance
Isolation method
Insulation resistance
Dielectric strength
Item
This is the number of safety output points on the Unit.
This is the polarity that the Unit uses to connect to output devices.
This is the maximum load current for outputs on the Unit. A specifica-
tion is given for each output and each Unit.
This is the rated voltage of the outputs on the Unit.
This is the number of slave connections that the Unit can have through
FSoE. You can perform communications with one FSoE master device
per connection.
The I/O refreshing methods that are used by the Unit.
The type of terminal block and connector that is used for connecting
the Unit. This specification includes the number of terminals for a
screwless clamping terminal block.
This gives the names and the layout of the indicators on the Unit.
Specification
0 to 55°C
10% to 95% (with no condensation or icing)
Must be free from corrosive gases.
−25 to 70°C (with no condensation or icing)
2,000 m max.
Pollution degree 2 or less: Conforms to JIS B 3502
and IEC 61131-2
Conforms to IEC 61131-2, 2 kV (power supply line)
CLASS III (SELV)
Category II: Conforms to JIS B 3502 and IEC 61131-2
Zone B
Conforms to IEC 60068-2-6
5 to 8.4 Hz with amplitude of 3.5 mm
8.4 to 150 Hz, acceleration of 9.8 m/s
100 min. in each X, Y, and Z directions (10 sweeps of
10 min. each = 100 min. total)
Conforms to IEC 60068-2-27
2
147 m/s
, 3 times in each X, Y, and Z directions
Photocoupler isolation
20 MΩ between isolated circuits (at 100 VDC)
510 VAC between isolated circuits for 1 minute at a
leakage current of 5 mA max.
DIN Track (IEC 60715 TH35-7.5/TH35-15)
Specification