7 Checking Operation and Actual Operation
4
On the Safety CPU Unit Setup and Programming View, perform one of the following opera-
tions.
• Select Mode – DEBUG Mode from the Controller Menu.
• Press the Ctrl + 2 Keys.
• Click the DEBUG Mode Button on the toolbar.
The following mode confirmation dialog box is displayed.
5
Click the Yes Button.
The following Connect to safety device Dialog Box is displayed.
Note 1. When you change the operating mode for the first time, the above dialog box is displayed and
Note 2. You do not need to enter anything in the Instance identification Box.
6
Click the OK Button.
The following transfer confirmation dialog box is displayed.
7
Check the safety of the system and then click the Yes Button.
The following password confirmation dialog box is displayed.
7 - 18
allows you to set the node name. You can change the factory-default node name of the Safety
CPU Unit.
If you do not want to change the node name, leave the field blank and click the OK Button. Re-
fer to 7-8 Node Name on page 7 - 50 for details on the node name settings.
NX-series Safety Control Unit User's Manual (Z930)