Omron NX-SL3300 User Manual page 99

Nx series safety control unit
Hide thumbs Also See for NX-SL3300:
Table of Contents

Advertisement

Item
Installation
orientation
and restric-
tions
Protective
functions
*1.
Only NX102 CPU Units and Communication Control Units can be connected. NX1P2 CPU Units cannot be
connected.
l NX-SOD400
Item
Number of safety output
points
Internal I/O common
Maximum load current
Rated input voltage
Number of safety slave
connections
NX-series Safety Control Unit User's Manual (Z930)
Installation orientation:
Connected to a CPU Unit or a Communication Control Unit
Possible in the upright installation orientation.
Connected to a Communications Coupler Unit
Six possible orientations.
Restriction: For upright installation, the ambient temperature is restricted as shown below ac-
cording to the total Unit load current.
4
3
2
1
0
0
10
20
30
Ambient Operating Temperature (°C)
For all installation orientations other than upright installation, the ambient temperature is re-
stricted as shown below according to the total Unit load current.
4
3
2
1
0
0
10
20
30
Ambient Operating Temperature (°C)
Overvoltage protection circuit and short detection
4 points
PNP (sourcing outputs)
0.5 A/point and 2.0 A/Unit
24 VDC (20.4 to 28.8 VDC)
1
Specification
2.5 A
40
50
55
40
50
Specification
2 Specifications
*1
2 - 33
2