12 Troubleshooting
Event code
Event name
65280000 hex
Stuck-at-
high Detect-
ed at Safety
Output
l Other Errors
Event code
Event name
80220000 hex
NX Message
Communica-
tions Error
l User Access Log
Event code
Event name
90400000 hex
Event Log
Cleared
90430000 hex
Memory All
Cleared
12 - 30
Meaning
It was detected that
The positive power supply line
the safety output ter-
is in contact with the output
minal is stuck ON.
signal line.
The output power supply is
outside the specifications.
The internal circuit is faulty.
A memory error or signal error
occurred due to a transient
cause, such as a software er-
ror or excessive noise.
Meaning
An error was detect-
The message communications
ed in message com-
load is high.
munications for an
The communications cable is
NX Unit and the mes-
disconnected or broken.
sage frame was dis-
Message communications
carded.
were cut off as the result of ex-
ecuting a synchronization or
restoration operation on the
Sysmac Studio or as the result
of disconnecting an EtherCAT
slave.
Meaning
The event log was
The event log was cleared by the
cleared.
user.
The Unit settings
The Clear All Memory operation
were cleared.
was performed.
M
Assumed cause
a
j
M
Assumed cause
a
j
M
Assumed cause
a
j
NX-series Safety Control Unit User's Manual (Z930)
Level
I
M
O
Reference
P
n
i
b
rt
f
n
s
o
¡
page
12 - 87
Level
I
M
O
Reference
P
n
i
b
rt
f
n
s
o
¡
page
12 - 88
Level
I
M
O
Reference
P
n
i
b
rt
f
n
s
o
¡ page
12 - 89
¡ page
12 - 89

Advertisement

Table of Contents
loading

Table of Contents