NX Unit power consumption
Current consumption from I/O power supply
Weight
Installation orientation and restrictions
*1.
The cable length for the Units that supply power to the corresponding Unit must be up to 20 m.
*2.
Only NX102 CPU Units can be connected. NX1P2 CPU Units cannot be connected.
l NX-SL3500
Maximum number of safety I/O points
Program capacity
Number of safety I/O connections
Number of CIP Safety originator connections
Number of CIP Safety target connections
Number of originators that can be connected
with a multi-cast connection
Number of FSoE master connections
I/O refreshing method
External connection terminals
Indicators
Hardware switch settings
Dimensions (mm)
I/O power supply method
Current capacity of I/O power supply terminals No I/O power supply terminals
NX Unit power consumption
Current consumption from I/O power supply
Weight
NX-series Safety Control Unit User's Manual (Z930)
Item
*1
Item
*1
Specification
Connected to a CPU Unit
1.25 W max.
Connected to a Communications Coupler Unit
0.90 W max.
No consumption
75 g max.
Installation orientation:
*2
Connected to a CPU Unit
Possible in the upright installation orientation.
Connected to a Communications Coupler Unit
Six possible orientations.
Restriction: None.
Specification
1,024 points
2,048 KB
128
0
0
0
128
Free-Run refreshing
None
[FS] LED, [VALID] LED, [DEBUG] LED, [TS] LED, [RUN]
LED
None
30 × 100 × 71 mm (W × H × D)
Not supplied.
Connected to a CPU Unit
1.25 W max.
Connected to a Communications Coupler Unit
0.90 W max.
No consumption
75 g max.
2 Specifications
2
2 - 5

Advertisement