6 Diagnostics

6 Diagnostics
Power
Connection/
voltage error
Cross-circuit
Short circuit
Fault in reset
circuit
Fault with
internal
cause
10
○ – LED off
● – LED on
Table 1: Diagnostic description
K1
K2
Fault
Supply voltage not present.
Supply voltage too low.
The enable circuits are connected incorrectly
or not connected at all.
Between both enable circuits S11- S12 and
S11-S22.
Error detection on next demand.
E.g., for emergency stop or safety door.
Between both enable circuits S11- S22 and
S11-S12.
Error detection on next demand.
E.g., for emergency stop or safety door.
Between both enable circuits S12 and S22.
The fault is not detected by the module itself.
E.g., for light grid type 4.
Between contact points A1 and A2.
Between S11 and S12.
Fault detection on next demand.
Between S11 and S22.
Fault detection on next demand.
Faulty reset button.
Short circuit between S33 and S34.
No fault detection on initial start, only on first
new demand.
Enable contact(s) of K1 faulty.
Enable contact(s) of K2 faulty.
Enable contact(s) of K1 and K2 faulty.
ESR5-BWS-31-24VAC-DC 12/19 MN049005EN www.eaton.com
Remedy
Apply supply voltage.
Adjust supply voltage.
Check the connection of the enable
circuits.
Remove cross-circuit.
Remove short circuit.
Remove short circuit.
Replace safety relays.