Configuring 24-Point I/O Points

Overview

Configuring 24-Point Input
Points
Technical Manuals Online! - http://www.tech-man.com
The 4010 allows you to use the 4605 24-Point I/O card to monitor input points
(switches) and control output points (Lamps, Tone-alerts, and Relays).
Use the following steps to configure input points on the 24-Point I/O card.
1.
Press <MENU>.
2.
Press <NEXT> or <PREVIOUS> until [PROGRAMMING] is displayed
and then press <ENTER>. A warning appears, indicating that the 4010 is
no longer in the Fire Alarm Operation mode.
Please Wait . . .
Fire Alarm Operation Suspended
3.
Press <ENTER> to continue.
Press <NEXT> or <PREVIOUS> until <CONFIGURE POINTS> is
4.
displayed and then press <ENTER>.
5.
Press <NEXT> or <PREVIOUS> to scroll through your choices until <24
IO INPUTS> is displayed and then press <ENTER>.
Use <NEXT> or <PREVIOUS> to scroll through your points until the
6.
desired point is displayed and then press Enter.
Press <NEXT> or <PREVIOUS> to scroll through your list of choices until
7.
the desired option is displayed and then press Enter. Your options are
shown in Table 6-6.