Software Point Types,
Relay Point Types
Technical Manuals Online! - http://www.tech-man.com
Continued
The 4010 includes two AUX relay points configured as AUX1 and AUX2. The
default point type settings for AUX1 set as an Alarm relay on until reset (point
type = RRELAY) and AUX2 set as a Trouble/Supervisory relay on until clear
(point type = TRELAY).
Table A-7 lists the Relay point types and their descriptions.
Table A-7. Relay Point Types
Point Type
RELAY
PRIMARY
ALTERN
AHUR
AHUO
AHUF
SRELAY
RRELAY
TRELAY
BRELAY
DHOLDER
SWATER
RWATER
RSUPV
SVISUAL
RVISUAL
SUPREL
SIGNAL
A-7
Description
Generic relay
Elevator Capture - primary
Elevator Capture - alternate
AHU on/off relay - single relay control
AHU on relay - dual relay control
AHU off relay - dual relay control
Alarm Relay - on 'til silence
Alarm relay - on 'til reset
Trouble relay - on til clear
Trouble relay - on til acknowledge
Door Holder
Waterflow relay - on 'til silence
Waterflow relay - on 'til reset
Supervisory relay
Visual - on 'til silence
Visual - on 'til reset
Suppression (agent discharge) release output
Generic Signal (no default operation)