Table A-5 lists the monitor point types and their descriptions.
Table A-5. Monitor Point Types
Point Type
Description
FIRE
Fire alarm (generic)
WATER
Waterflow switch
HEAT
Heat detector
DUCT
Duct detector
FLAME
Flame detector
PULL
Pull station - manual
SMOKE
Smoke detector
VSMOKE
Verified smoke zone
ABORT
Abort Zone (pre-signal)
EMERG
Emergency Alarm
SFIRE
Combination Smoke/Fire zone
VSFIRE
Verified Combination Smoke/Fire zone
SPULL
Combination Smoke/Pull zone
VSPULL
Verified Combination Smoke/Pull zone
GENMON
Generator monitor
SGENMON
Supervisory generator monitor
FPUMP
Fire pump monitor
SFPUMP
Supervisory fire pump monitor
S2STAGE
2-stage monitor (abn=pre-signal, short=alarm)
SO
Sprinkler supervision (normally open)
WSO
Waterflow/sprinkler supervision (normally open)
LATSUPV
Latching supervisory
SDUCT
Supervisory Duct Detector
SUPDET
Suppression Release detector zone
SUPABRT
Suppression Release abort zone
SUPDUMP
Suppression Release manual dump
SUPPRES
Suppression Release pressure monitor
SUPV
Supervisory (generic)
UTIL
Non-alarm utility
DAMPER
Damper Monitor (open/closed)
TROUBLE
Trouble monitor
STYLEC
Current limit = fire alarm, short/open = trouble
GVMON
Generic verified monitor
A-5