Active Status Reminder

Overview

Setting the Active Status
Reminder
Technical Manuals Online! - http://www.tech-man.com
The Active Status Reminder option allows you to set an interval and duration in
which the 4010 reminds operators of the FACP that a FIRE, SUPV, or TBL
condition still exists in the panel. Your choices are as follows:
ON/OFF Status (turn the option ON or OFF). A setting of ON activates
the option with a default Reminder Interval of 8 hours with a 5-second
Acknowledge Option signal duration.
Reminder Interval (set a reminder interval from 1-12 hours).
Acknowledge Option (set a signal duration of 1-60 seconds). A setting
of 0 seconds has the following effect:
-
For a Trouble condition, the signal sounds until the condition is
acknowledged at the front panel.
-
For an Alarm (FIRE) condition, the signal sounds until the alarm
condition is cleared.
Use the following steps to set the Active Status Reminder on the 4010 FACP.
1.
Press <MENU>.
2.
Press <NEXT> or <PREVIOUS> until [PROGRAMMING] is displayed
and then press <ENTER>. A warning appears, indicating that the 4010 is
no longer in the Fire Alarm Operation mode.
3.
Press <ENTER> to continue.
Press <NEXT> or <PREVIOUS> until <SYSTEM OPTIONS> is
4.
displayed and then press <ENTER>.
5.
Press <NEXT> or <PREVIOUS> to scroll through your choices until
<ACTIVE STATUS REMINDER> is displayed and then press <ENTER>.
6.
Press <NEXT> or <PREVIOUS> to scroll through the options until On/Off
Status is displayed and then press Enter.
7.
Press <NEXT> or <PREVIOUS> to select ON or OFF and then press
Enter. Follow the prompts to confirm this action.
8.
Press <NEXT> or <PREVIOUS> to scroll through the options until
Reminder Interval is displayed and then press Enter.
9.
Press <NEXT> or <PREVIOUS> to select an interval from 1-12 hours and
then press Enter. Follow the prompts to confirm this action.
10. Press <NEXT> or <PREVIOUS> to scroll through the options until
Acknowledge Option is displayed and then press Enter.
11. Press <NEXT> or <PREVIOUS> to select an signal duration from 0-60
seconds and then press Enter. Follow the prompts to confirm this action.