System Power-Up and Checkout, Continued
Power-Up and Checkout
(continued)
Technical Manuals Online! - http://www.tech-man.com
If the 4010 passes its start up self-test, the FACP starts and the system is normal,
the High-Level Status screen shown in Figure 3-10 displays. If troubles exist in
the system, Figure 3-11 displays after pressing <ACK>.
Note:
The High-Level Status screen is the first screen shown on a 4010
whether in a normal or a trouble/supervisory/fire alarm state
before any keys are pressed.
Figure 3-10. System Normal (High Level Status) Screen
FIRE=0
[TrueAlarm]
Custom Label
FIRST FLOOR EAST WING ROOM 12
Smoke Detector
Point Type
Note:
If the self-test fails, the 4010 displays the error code and waits 45
seconds before attempting a restart. Refer to Chapter 10 for a
list of error codes.
Checkout
Caution:
•
Notify the fire department and the central alarm receiving station if
transmitting alarm conditions.
•
Notify building personnel of the test so that alarm sounding devices are
disregarded during the test session.
•
When necessary, disable activation of alarm notification appliances and
speakers to prevent their sounding.
SYSTEM IS NORMAL
10:09:33am
Wed 27-Aug-97
SUPERVISORY=0
Trouble
Figure 3-11. System Trouble Screen
Before proceeding with the acceptance test procedures, do
the following:
3-11
TROUBLE=3
Add
1/130
1/3
Device Condition
Continued on next page
First of
Three