Door Drop on AC Loss
Overview
Setting the Door Drop on AC
Loss Timer
Technical Manuals Online! - http://www.tech-man.com
The Door Holder - AC Fail Door Drop Timer allows the 4010 to hold doors
open for a set duration during an AC power loss condition. After that duration
has expired, the 4010 shuts off the door holder devices and the doors close. The
range for the timer is 0-60 minutes, with a default setting of 5 minutes. To have
door holders drop the doors immediately upon AC power loss, set the timer to
zero minutes.
Use the following steps to set the Door Holder AC Fail Door Drop timer on the
4010 FACP.
1.
Press <MENU>.
2.
Press <NEXT> or <PREVIOUS> until [PROGRAMMING] is displayed
and then press <ENTER>. A warning appears, indicating that the 4010 is
no longer in the Fire Alarm Operation mode.
3.
Press <ENTER> to continue.
4.
Press <NEXT> or <PREVIOUS> until <SYSTEM OPTIONS> is
displayed and then press <ENTER>.
5.
Press <NEXT> or <PREVIOUS> to scroll through your choices until
<DOOR DROP ON AC LOSS> is displayed and then press <ENTER>.
Press <NEXT> or <PREVIOUS> to set the timer from 0-60 minutes and
6.
then press Enter.
7.
Follow the prompts to confirm this action.
7-8
Need help?
Do you have a question about the 4010 and is the answer not in the manual?
Questions and answers
On a 4010 what is point label 4009A trouble. I **** not familiar with this