On a 4010 what is point label 4009A trouble. I **** not familiar with this
1 comments:
Mr. Anderson
May 14, 2025
A point label trouble on a Simplex 4010 related to a 4009A booster may indicate that the point assigned to the booster is not properly configured or is experiencing communication issues. This could be due to incorrect dip switch settings, wiring issues, or the point type not being correctly set in the system configuration. All 4009 NACs are automatically set for Class B operation and assigned a point type of SSIGNAL, but manual programming may be needed if Quick CFIG does not resolve the issue.
Need help?
Do you have a question about the 4010 and is the answer not in the manual?
Questions and answers
On a 4010 what is point label 4009A trouble. I **** not familiar with this
A point label trouble on a Simplex 4010 related to a 4009A booster may indicate that the point assigned to the booster is not properly configured or is experiencing communication issues. This could be due to incorrect dip switch settings, wiring issues, or the point type not being correctly set in the system configuration. All 4009 NACs are automatically set for Class B operation and assigned a point type of SSIGNAL, but manual programming may be needed if Quick CFIG does not resolve the issue.