Configuring TrueAlarm Points
Overview
Add IDNet Point
Edit TrueAlarm Point
Technical Manuals Online! - http://www.tech-man.com
This section describes how to Add an IDNet Point, Edit a TrueAlarm Point, and
Delete a TrueAlarm Point.
Use the following steps to Add an IDNet point to the 4010 FACP.
1.
Press <MENU>.
2.
Press <NEXT> or <PREVIOUS> until [PROGRAMMING] is displayed
and then press <ENTER>. A warning appears, indicating that the 4010 is
no longer in the Fire Alarm Operation mode.
Please Wait . . .
Fire Alarm Operation Suspended
3.
Press <ENTER> to continue.
Press <NEXT> or <PREVIOUS> until <CONFIGURE POINTS> is
4.
displayed and then press <ENTER>.
5.
Press <NEXT> or <PREVIOUS> to scroll through your choices until
<TRUEALARM> is displayed and then press <ENTER>.
Use <NEXT> or <PREVIOUS> to scroll through your choices until <Add
6.
IDNet Point> is displayed and then press Enter.
7.
The first unused point in the system (for example, M1-1) is displayed. Press
<NEXT> or <PREVIOUS> to scroll through your list of unused points
until the desired point is displayed and then press Enter.
8.
Follow the prompts to confirm this action.
Note:
If there are 250 devices present in the 4010 (maximum allowed), the
system informs you that the IDNet channel is full and does not allow
you to add any more points.
Use the following steps to Edit a TrueAlarm point in the 4010 FACP.
1.
Press <MENU>.
2.
Press <NEXT> or <PREVIOUS> until [PROGRAMMING] is displayed
and then press <ENTER>. A warning appears, indicating that the 4010 is
no longer in the Fire Alarm Operation mode.
Please Wait . . .
Fire Alarm Operation Suspended
3.
Press <ENTER> to continue.
Press <NEXT> or <PREVIOUS> until <CONFIGURE POINTS> is
4.
displayed and then press <ENTER>.
5.
Press <NEXT> or <PREVIOUS> to scroll through your choices until
<TRUEALARM> is displayed and then press <ENTER>.
6-3
Continued on next page