Card Summary By Location (See Figure 6); System Point Summary (See Figure 7); Zone Name; Address - Simplex 4100 Installation Manual

Fire alarm system
Hide thumbs Also See for 4100:
Table of Contents

Advertisement

4100/4120 INSTALLATION MANUAL

2. Card Summary by Location (see Figure 6)

The Card Summary by Location shows the number of cards within the system. This page should be used to
verify delivery of system cards from the factory. It also shows a decimal card number which is the address for
that printed circuit board. Addresses 3 and 9 are shown below on Custom Terminal Wiring Identifiers.
--------------------------------------------------------------------------------
XYZ BUILDING 1
909015J node:1 rev:1
--------------------------------------------------------------------------------
CARD LOCATION LISTING:
LOCAL CONTROLLER UNIT:
DAUGHTER CARDS:
Card
-----
ANNUNCIATORS:
Annun Card
----- -----
0
NO REMOTE CARDS IN SYSTEM

3. System Point Summary (see Figure 7)

The System Point Summary is of primary importance to the installer. Simplex personnel must provide this
information prior to installation. Call your local Simplex branch office, which is listed in the Yellow Pages, and
request this information be provided. This is used in conjunction with the Layout pages, to determine wiring
terminations and the information shown below.
3.1

Zone Name

Zone names reference the custom label to specific points for actual customer wiring. They include monitor
zones (ZNx), signals (SIGx), auxiliary relays (AUXx), 24 point I/O (PMx) and feedback (FBx) numbers.
Zones, signals, relays, feedbacks, etc., are shown in numerical sequence.
3.2

Address

Each printed circuit board requires a unique address. Address 0 identifies the master termination module.
Up to 119 addresses, one per printed circuit board, may be used in a system. Addresses may or may not
be in sequential order, but the report always starts with address 0. Two address labels are used for each
mother/daughter board combination. The mother board will have its unique address label next to the P.C.
board connector. The daughter board will have an identical label.
Document No: 4100-M002
CARD SUMMARY BY LOCATION
Card Type
----------------------------------------
0
(7003) 4100+ Master Controller
1
(3003) 8 Pt, 3 Amp Relay w/ Feedback
2
(3003) 8 Pt, 3 Amp Relay w/ Feedback
3
(0112) 2120/RS232 Interface
4
(6005) Power Supply/Charger
6
(0110) MAPNET Interface
7
(0110) MAPNET Interface
8
(0140) 4120 Network Interface
Card Type
----------------------------------------
0
64 LED / 64 Sw Controller
5
(0301) 64 LED / 64 Sw Controller
Card Summary by Location
Figure 6
8
Page
05:20:54, THU, 08-MAY-97
LOCATION
Zone Range
-----------------
AUX3-10
AUX11-18
RS232-1, RS232-2
M1-1 - 127
M2-1 - 127
Zone Range
-----------------
Issue 1.0
3
CARD

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

4120

Table of Contents