Custom Control Programming,
Output Side (THEN)
(Continued)
Technical Manuals Online! - http://www.tech-man.com
Continued
FIELD 1
Field 1 contains the Action Operators listed in Table 8-3.
FIELD 2
When using any action operator, Field 2 choices are:
CPU Card Points
System Card Points
Power Supply Points
Digital Pseudo Points
List Pseudo Points
FIELD 3
Field 3 contains the Set and Reset Priorities of control equipment (relays) and
Pseudo points. This eliminates confusion of when a point is under control of one
statement and another statement tries to take control (see Figure 8-31).
Field 1
OUTPUT
[Hold On]
STATEMENT
In Figure 8-32, point 23-02 will HOLD ON (IF the Input is true) at a Set priority
of 9. This Output statement will maintain control of this point until another
output statement with an equal (9) or greater Set priority takes over. The
possible ranges for a priority are from 1 to 15, 1 being the highest and 15 being
the lowest priority. By default, the priority is 9. When changing a priority, press
Function and then press <ö> to place the cursor under the Set priority. Use
<Next> and <Previous> to scroll through the priorities.
Press <ö> to place the cursor under the Reset priority. Use <Next> and
<Previous> to scroll through the priorities and then press <Enter> to program
the priorities selected.
Field 2
[23-02]
Action
Specifier for
Field 2
Figure 8-33
8-25
Field 3
[9,9]
Point
Set Priority
Reset
Priority