Depleted Battery Cut-Out; Overview; Setting The Depleted Battery Cut-Out - Simplex 4010 Installing And Operating Insructions

Front panel
Hide thumbs Also See for 4010:
Table of Contents

Advertisement

Depleted Battery Cut-Out

Overview

Setting the Depleted Battery
Cut-Out
Technical Manuals Online! - http://www.tech-man.com
This option selects the mode of operation for the 4010 FACP if an alarm occurs
during an AC power loss while a Depleted Battery trouble exists. The specific
operation of this option differs slightly, depending on whether you have a
domestic or Canadian system.
Domestic Operation. The default setting for the option is OFF and the
threshold voltage is 19.4 VDC ± 5%. Operation of this option for a domestic
system is as follows:
If the system is in alarm and a depleted battery condition occurs, any NACs
that are active remain active.
If the system in not in alarm and a depleted battery condition occurs, the
NACs are prevented from activating.
Canadian Operation. The default setting for the option is OFF and the
threshold voltage is 19.4 VDC ± 5%. Operation of this option for a Canadian
system is as follows:
When a depleted battery condition occurs, power is turned off to the 4010.
AC power must be restored to re-activate the 4010.
Use the following steps to set the Depleted Battery Cut-Out on the 4010 FACP.
1.
Press <MENU>.
2.
Press <NEXT> or <PREVIOUS> until [PROGRAMMING] is displayed
and then press <ENTER>. A warning appears, indicating that the 4010 is
no longer in the Fire Alarm Operation mode.
3.
Press <ENTER> to continue.
Press <NEXT> or <PREVIOUS> until <SYSTEM OPTIONS> is
4.
displayed and then press <ENTER>.
5.
Press <NEXT> or <PREVIOUS> to scroll through your choices until
<DEPLETED BATT. CUTOUT> is displayed and then press <ENTER>.
Press <NEXT> or <PREVIOUS> to set the option to ON or OFF and then
6.
press Enter.
7.
Follow the prompts to confirm this action.
7-11

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents