Pseudo Points,

List Pseudo Points

4010 System Lists

Technical Manuals Online! - http://www.tech-man.com
Continued
List pseudo points provide a convenient way to group points in any manner the
user desires. The 4010 contains two list pseudo cards - one reserved for the
system and one for the user. The status of the list is determined by counts which
are maintained for the following states:
Fire Count
Supervisory Count
Open
Fire Ack
Supervisory Ack
On/Input
Manual Control
The 4010 restricts the total number of points in any one list to 255. It also
restricts the total number of points available on any one list card to 500 (the total
number of points in all lists on one list card cannot exceed 500).
The 4010 system reserves one list card at address 22 for system use. Currently,
12 of the 25 system lists are used by the 4010 application. All of these lists
control application specific operation of the 4010 panel. Some are
auto-generated by the system as points are added and may not be edited, while
the remainder are filled by the user to activate pre-defined applications. The
system lists are shown in Table B-22.
Trouble Count
Normal
Short
Limited
Trouble Ack
Disable
On/Coding
B-19
Continued on next page