Accept Default Settings for System Options

Procedure

Technical Manuals Online! - http://www.tech-man.com
1.
Press <MENU>.
Press <NEXT> or <PREVIOUS> until [Quick CFIG] is displayed and
2.
then press <ENTER>. A warning appears, indicating that the that the 4010
is no longer in the Fire Alarm Operation mode.
Please Wait . . .
Fire Alarm Operation Suspended
3.
Press <ENTER> to continue with the Quick-CFIG option.
4.
Press <NEXT> or <PREVIOUS> until <ACCEPT DEFAULT
OPTIONS> is displayed and then press <ENTER>. A warning appears,
indicating that this operation may change current settings.
WARNING
<Enter> to Continue
This may CHANGE current setting
5.
Press <ENTER> to continue. The following message appears, indicating
that the system is restoring the default settings for system options.
**
Default Settings Restored
4-5
WARNING
**

Advertisement

Table of Contents
loading
Need help?

Need help?

Do you have a question about the 4010 and is the answer not in the manual?

Questions and answers

Pete
March 7, 2025

On a 4010 what is point label 4009A trouble. I **** not familiar with this

User image 67cb254f3b885
1 comments:
Mr. Anderson
May 14, 2025

A point label trouble on a Simplex 4010 related to a 4009A booster may indicate that the point assigned to the booster is not properly configured or is experiencing communication issues. This could be due to incorrect dip switch settings, wiring issues, or the point type not being correctly set in the system configuration. All 4009 NACs are automatically set for Class B operation and assigned a point type of SSIGNAL, but manual programming may be needed if Quick CFIG does not resolve the issue.

This answer is automatically generated

Table of Contents

Save PDF