System Power-Up and Checkout,
Acceptance Test
Technical Manuals Online! - http://www.tech-man.com
Continued
When finished with the original installation and all modifications, conduct a
complete operational test on the entire installation to verify compliance with
applicable NFPA standards. Testing should be conducted by a Simplex-trained
technical representative in the presence of a representative of the Authority
Having Jurisdiction, and the customer's representative. Follow the procedures
outlined in Chapter 7 "Inspection, Testing, and Maintenance" of NFPA Standard
72-1996 and the following steps.
1.
Activate an initiating device (smoke, pull, etc.) and check that all active
notification appliances (strobes, horns, etc.) function. Reset the alarm
initiating device, the FACP, and any other associated equipment. Repeat
this step for each initiating device.
2.
Remove AC power, activate an initiating device, and check that active
notification appliances sound, and alarm indicators illuminate. Measure the
battery voltage with notification appliances active. Replace any battery with
a voltage of less than 24VDC and reapply AC power.
Note:
Step 2 requires fully charged batteries. If batteries are new or
discharged due to a recent power outage, allow the batteries to charge
for 48 hours before testing. Refer to "Periodic Testing and
Maintenance" section for more information on testing batteries.
3.
Reapply AC power and check that all yellow and red LEDs are OFF and the
green AC Power LED is ON.
Caution:
Notify fire, central station, and/or building personnel when
you finish testing the system.
3-12
Need help?
Do you have a question about the 4010 and is the answer not in the manual?
Questions and answers
On a 4010 what is point label 4009A trouble. I **** not familiar with this
A point label trouble on a Simplex 4010 related to a 4009A booster may indicate that the point assigned to the booster is not properly configured or is experiencing communication issues. This could be due to incorrect dip switch settings, wiring issues, or the point type not being correctly set in the system configuration. All 4009 NACs are automatically set for Class B operation and assigned a point type of SSIGNAL, but manual programming may be needed if Quick CFIG does not resolve the issue.
This answer is automatically generated