Point Type Messages for Monitor Points

Monitor Points

Technical Manuals Online! - http://www.tech-man.com
There are 32 Monitor Points available with the 4005. These are described in
Figures 5-6 through 5-33.
Pt. TYPE: SFIRE
Description: Smoke/Fire Combination Zone
Circuit Status
LCD Readout (2
Normal
Fire monitor Zone
Limited
Fire monitor Zone
Open
Fire monitor Zone
Short
Fire monitor Zone
Disable TBL
Fire monitor Zone
Class A TBL
Fire monitor Zone
Used when Smoke Detectors and shorting type devices
Detailed Description:
are used on the same circuit.
Figure 5-6. SFIRE Point Type
Pt. TYPE: VFIRE
Description: Verified Smoke/Fire Combination
Circuit Status
LCD Readout (2
Normal
Fire monitor Zone
Limited
Fire monitor Zone
Open
Fire monitor Zone
Short
Fire monitor Zone
Disable TBL
Fire monitor Zone
Class A TBL
Fire monitor Zone
Detailed Description:
Used to activate the alarm verification software for all
smoke detectors connected to this circuit. All shorting devices will cause an
immediate alarm.
Figure 5-7. VFIRE Point Type
Pt. TYPE: SPULL
Description: Smoke/Pull Combination Zone
Circuit Status
LCD Readout (2
Normal
Fire monitor Zone
Limited
Fire monitor Zone
Open
Fire monitor Zone
Short
Fire monitor Zone
Disable TBL
Fire monitor Zone
Class A TBL
Fire monitor Zone
Used when only Smoke Detectors and Pull Stations are
Detailed Description:
connected to the circuit.
Figure 5-8. SPULL Point Type
5-3
nd
line)
NORMAL
ALARM
TROUBLE
ALARM
TROUBLE
TROUBLE
nd
line)
NORMAL
ALARM
TROUBLE
ALARM
TROUBLE
TROUBLE
nd
line)
NORMAL
ALARM
TROUBLE
ALARM
TROUBLE
TROUBLE