5.1

Configuring the 2008 LCD Annunciator

5.1.1

Powering the Annunciator in conventional mode.

1.
Address switch SW9-1 must be in the OFF position. That is, conventional mode.
2.
Insert the key into the key switch and rotate it 90 degrees anticlockwise.
3.
For the first time that power is applied:
a.
Ensure that the communication cable is not connected between the FACU and the Annunciator.
Press and hold the RESET key before power is applied.
b.
c.
Connect the Annunciator to the power supply or to the panel.
d.
After the Annunciator is powered up, wait 5 seconds, then release the RESET key.
e.
Wait until Comm Failure message is displayed.
5.1.2

Annunciator configuration menu

CAUTION: To ensure that you do not make any unintended changes, a timeout of 30 seconds is implemented. If you do not press any
key in less than 30 seconds, you are automatically logged out.
To enter the configuration menu, press and hold the ENTER key for at least 5 seconds.
1.
2.
After the ENTER key is released, the Annunciator displays the configuration menu. Use the Up and Down keys to scroll through
configuration menus. For example the following screen shows the option to set the Annunciator's address.
3.
The configuration options are:
-
Set Annunc Address
-
Set Ann. Language
-
Software Rev
-
Contrast
-
Brightness
-
Exit
4.
After a configuration option is displayed, press and hold the ENTER key for at least 2 seconds. After the ENTER key is released
after at least 2 seconds, actual setting options are displayed.
5.
Use the Up and Down keys to set different values. For example, change the address. The address range is 4 to 7.
6.
After the chosen value is set, to save the settings, press the ENTER key.
5.1.3

Changing the address of the 2008 LCD Annunciator address using the LCD Annunciator

Valid address values are from four to seven. If the Annunciator ID is not set in the Annunciator or there is a communication error between
the FACU and the Annunciator, the Annunciator UI displays error message Comm Failure.
5.1.4

Changing the language of the LCD Annunciator

From the menu, you can select the language to be Spanish, English or Portuguese.
5.1.5

Checking the software version of the LCD Annunciator

The Annunciator displays the software version on the LCD screen. For the software version, no other configuration needs to be done.
5.1.6

Changing the display contrast of the LCD Annunciator

The Annunciator displays the current contrast value on the LCD screen. You can vary the contrast level from 0% to 100% in steps of 10%.
5.1.7

Changing the display brightness of the LCD Annunciator

The Annunciator displays the current brightness value on the LCD screen. You can vary the brightness level from 0% to 100% in steps of
10%
page 12
MENU:
Set Annunc Address
Foundation Series 2606-9101 LCD Annunciator Installation Guide
579-1434 Rev B