Handling Abnormal Conditions

Normal Operation

Abnormal Conditions

Technical Manuals Online! - http://www.tech-man.com
The 4010 shows the following under normal conditions:
Green AC power LED ON (indicating that AC power is applied)
All other panel indicator LEDs OFF
System Information on the LCD (SYSTEM NORMAL with the current time
and date)
Abnormal conditions are indicated on the 4010 by flashing the alarm,
supervisory, or trouble LED and sounding the tone-alert. The display provides
information as to the point status (alarm, supervisory, and trouble), time, date,
type of device (smoke detector, pull station, etc.), number of abnormal
conditions in the system, and a custom description of the abnormal condition
causing the alarm. Alarm, supervisory, and trouble conditions each have their
respective acknowledge key. Pressing the appropriate acknowledge key silences
the tone-alert. However, the LED indicator remains ON until all initiating
devices are restored to normal.
Custom Label
FIRST FLOOR EAST WING ROOM 12
Smoke Detector
Point Type
Figure 11-1. Example Abnormal Condition Screens
When the 4010 senses an Alarm Condition, the tone-alert sounds at a march time
rate, and the FIRE ALARM LED turns ON and flashes, indicating that an alarm
condition is present. In addition, the appropriate indications are shown on the
display.
When the 4010 senses a Supervisory Condition, the tone-alert sounds steady, the
SYSTEM SUPERVISORY LED turns ON and flashes, and various programmed
events occur.
When the 4010 senses a malfunction within the system (loss of power, hardware
failure, etc.), a Trouble Condition is announced by the system. The tone-alert
sounds steady, the SYSTEM TROUBLE LED flashes, and various programmed
events occur.
The tone-alert may be programmed to sound at specified time intervals to serve
as a reminder that any active status condition still exists within the system
(Active Status Reminder).
FIRE=0
SUPERVISORY=0
[TrueAlarm]
11-2
TROUBLE=3
Add
1/130
Trouble
1/3
Device Condition
Continued on next page
First of Three
Troubles

Hide quick links: